Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
Loading...
eSite Tools is a remote control and monitoring system (RMS), analysing and optimizing of the performance of all eSites in an entire network.
The system requires TCP/IP connectivity either via the built-in 3G modem or via the Ethernet connection.
eSite Tools is not a standard option, contact eSite Power Systems to get more information.
The status and connection state of all eSites in the network are listed and presented on a dashboard in eSite Tools. A list of time stamped alarms with colour codes showing the severity of the alarm is displayed. Connection status and alarms are also displayed on a map showing the location of all sites in the network. The dashboard offers search and filter functionality and can be customized. Data from the dashboard can be exported to PDF, XML, CSV and Excel.
All configurable data in eSite Web can also be configured in eSite Tools, as they are synchronized.
Variables
Data is transferred from eSite x10 to eSite Tools and settings are transferred from eSite Tools to eSite x10. By default, the time interval between the transfers is 10 minutes. This value can be customized under the eSite Tools configuration menu.
Alarms
Alarms are pushed from eSite x10 to eSite Tools and are instantly transferred without waiting for normal data synchronization.
Functions
Remote software updates and tuning of configuration parameters on eSite x10.
Each eSite x10 has a local logger that collects data into a local database. eSite x10 performs local aggregation and analytics on collected data to achieve accurate remote reporting and troubleshooting. Examples of such functionality include energy calculations that are performed with high resolution compared to doing such analysis on relatively low resolution data on the server side, which enables correct average calculations between any two data samples.
In case of interrupted communication between eSite Web and eSite Tools, data is buffered and automatically uploaded when there is communication.
eSite Tools has the ability to update configurations remotely of all connected sites. All configurable parameters can be visualized via the GUI. By selecting several sites in eSite Tools, the same set of configurations can be pushed to all selected sites at the same time.
It is also possible to backup and restore configurations between different sites.
Updates of firmware/software can be done via eSite Tools. If new updates or new option packages are available, it is easy to update several eSite x10 systems at once by selecting a group of sites in eSite Tools.
An example of data from one eSite connected to eSite Tools remote system is shown in figure 5.1.
Copyright © 2021 eSite Power Systems AB
This document describes how to operate and maintain eSite x10. It focuses on eSite x10, eSite Web, eSite Tools and the settings that can be done to the associated systems. For optional eSite accessories and installation of the associated systems see the Installation manual.
This document is intended for the personnel that will operate and maintain eSite x10. Such personnel can work both on site and from a distance via eSite Tools. All personnel must have sufficient basic skills and training.
Warning
Highlights hazards that may result in personal injuries and/or serious damage to mechanical structures and equipment.
Caution
Highlights hazards that may result in damage to the equipment.
Read
Highlights that there is information to read in addition to this document. That information must be considered when operating the device or control.
eSite™ and eSite Tools™ are registered trademarks of eSite Power Systems AB (publ) and will be referred to here after as eSite and eSite Tools.
Product Description
Installation Guide
Operations Manual
A
Ampere
Ah
Ampere hour
AC
Alternating Current
ATS
Automatic Transfer Switch
BMS
Battery Monitoring System
BMU
Battery Monitoring Unit
°C
Degree Celsius
CAN
Controller Area Network
CE
Conformité Européenne
DC
Direct Current
EC
European Conformity
EMC
Electromagnetic Compatibility
GND
Electrical Ground
HP
High Priority
Hz
Hertz
kW
Kilowatt
LP
Low Priority
MCB
Miniature Circuit Breaker
MPPT
Maximum Power Point Tracker
MHz
Megahertz
N/A
Not Available
NTP
Network Time Protocol
PVC
Polyvinyl chloride
RMS
Remote Monitoring System
SCR
Silicone controlled rectifiers
SOC
State of charge
SIM
Subscriber Identity Module
V
Volt
V
AC Volts of Alternating Current
V
DC Volts of Direct Current
W
Watt
WLAN
Wireless Local Area Network
Associated systems
The term associated systems refers to parts or systems outside eSite x10, e.g. the battery bank, the genset, the grid and the solar arrays.
Customer load
The customer load is the equipment that is supplied with power from eSite x10.
Main Compartment
The Main Compartment contains power electronics and the control system of eSite x10. The Main Compartment must not be opened.
Connection Compartment
The Connection Compartment is the connection point access to eSite x10.
Lower Main
The Lower Main is part of the Main Compartment. It is reached through the Connection compartment when the Main Compartment is docked. Signal cables and control cables are connected to the Lower Main.
eSite Tools
eSite Tools is an Remote Monitor and Control System that monitors several eSite x10 in a network. eSite Tools can be used to view the status of all sites in a network and to create a variety of reports. It can also be used for software downloading and for configuration changes.
eSite Web
eSite Web is the eSite x10 interface. It is used to monitor data and configure the system on the site.
Tenant
The tenant is the telecom operator that receives power through eSite x10. Each tenant can connect both high priority load and low priority load. The power consumption can be separately measured for the connected tenants.
eSite x10 is a carefully designed product that has undergone rigorous performance testing with regards to quality, environment, electrical safety and functionality.
This product and the system software has complied to and met the test standards of:
ETSI EN 300 386 V1.6.
ETSI 300 019-1-2 Class 2.
IEC/EN 60950-1:2005+A1+A11+A12+A2
IEC/EN 60950-22:2006-A11
eSite x10 RSC and RSY models both comply to the CE standards. EC (European Conformity) labels are found on both the Main Compartment (see figure 1.1) and the Connection Compartment (see figure 1.2).
eSite x10 product number (P/N) of the x10 follows the principle:\<Functions>-\<Index>/\<Region> where;
Function: R = Rectifier, S = Solar, I = Inverter, Y = supervision/control generation 1, C = supervision/control generation 2, E = Expansion, X = passive distribution, P = Protection device. Index: New variants of a base product are indicated by an increased Index, where the first version is 001. Region: /1 = Europe, Africa and Asia, /2 = North and South America, Caribien and Mexico, /3 = Australia and Islands in the pacific ocean.
RSY-001/1
Main Compartment with Solar, Rectifier and supervision/control
Used for main compartment starting with serial number 7246xxx
RSC-001/1
Main Compartment with Solar, Rectifier and supervision/control
Used for main compartment starting with serial number 7247xxx
RC-001/1
Main Compartment with Rectifier only and supervision/control
Used for main compartment starting with serial number 7250xxx
XP-001
Connection Compartment
Used for main compartment RSY and RSC. With the default MCB configuration
3 x 125A, 3 x 32A, 3 x 6A.
XPE-002
Connection Compartment for Expansion units
With site load increase (site load = 9 + 9 kW) Same pre-configuration and available options as for PE-001, but with the possibility to connect 9 kW load also to the expansion CC, with the default MCB configuration
3 x 125A, 3 x 32A, 3 x 6A.
RE-001/1
Rectifier Expansion
Mandatory region identifier
SE-001/1
Solar Expansion
Mandatory region identifier
eSite Power Systems operate a 'Service Desk & Knowledge Base', where the Customer can access certain documentation, guides and software, report Issues and request support/resolution of reported Issues.
The Customer may access the 'Service Desk & Knowledge Base' by using a user account (provided by the Supplier). The Service Desk is a single point of contact between the Supplier and the Customer and can be found here:
http://servicedesk.esitepowersystems.com
When reporting Issues or requesting support, the Customer is asked to fill in the appropriate form and describe the problem/request in detail. If applicable, photographs and/or log files may be attached to the request.
During work with electrical equipment precautions are necessary to make sure that the safety for personnel and property is sufficient and satisfactory. The safety instructions in the documents that belong to eSite must be followed during installation, testing, commissioning, maintenance, repair and removal of power and supervision of equipment.
eSite x10 has been certified in regard to personal safety according to IEC CB Test certificate issued by Intertek. Certificate reference number is SE-06031 and a copy with more information is available on eSite Power Systems home page.
Read
Site owner personal safety regulations are complemented by the information in this document. If the information in this document does not agree with the site owner regulations, the site owner regulation overrides this document. Ensure that you understand the site owner regulations.
Warning
Do not open or make modifications to the Main Compartment. It is strictly prohibited and can be a threat to life.
Warning
Personnel involved must have sufficient competence and training, if not there is a risk of injury to the personnel and a risk of damage to the equipment.
Warning
Keep the site clean and clear of redundant material to decrease the risk of accidents.
Add protection to prevent the Connection Compartment from being moist during work.
Always close the Connection Compartment lid when the work is complete.
Note information on equipment that identifies danger or gives information and make sure that all personnel are familiar with the information and understand the danger.
Do not remove labels that identify danger or give information about the equipment.
Only use tools and equipment for their intended use.
Warning
High energy and high voltage up to 480V AC are used to power equipment. High voltage poses a significant risk of electric shock. Batteries can contain large quantities of energy. To touch battery terminals directly or indirectly through cables or moist items can cause discharge of the contained energy. Fast discharge of contained energy can start a fire or cause serious injury or death to workers.
Metal objects such as rings, watches, bracelets, etc. that can cause short circuits in the equipment, must not be worn when working on or around live equipment.
Make sure that equipment and facilities are correctly grounded to keep the risk of personal injury and equipment damage to a minimum.
The tools that are used on live equipment must have factory insulation according to IEC 900 standards for hand tools. Tools that have insulating tape as insulation are not permitted.
The tools that are used must be inspected for damage before each shift. Do not try to repair defective tools on your own.
Installed cables must be clearly identified with labels.
All battery cables must have the two ends identified to prevent accidental short circuits.
Charged cells in a battery have a short circuit effect. A short circuit between the terminals can cause dangerous burns and a spark formation can make the cells burst.
Keep the working area clean.
It must be possible to disconnect the load and the AC- and the DC-supplies from the power supply system. The AC breakers must be installed so that all phases can be cut off in one step. Local rules must be obeyed.
The unit must be de-energized before work with power related connections above 24 V starts. Note that there can be more than one power source connected to eSite and that filters of eSite unit can be charged even if the supply voltage is disconnected.
Before the power supply to the equipment is set to on all tools and other objects not related with eSite must be removed.
© Copyright eSite Power Systems AB 2021. All rights reserved.
No part of this document may be reproduced in any form without the written permission of the copyright owner. The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. eSite Power Systems AB shall have no liability for any error or damage of any kind resulting from the use of this document.
https://www.clearbluetechnologies.com/
E-mail: support@clearbluetechnologies.com
Phone: +1 647 748 4822
Clear Blue Technologies 30 Lesmill Road, Unit 7 Toronto, ON, Canada M3B 2T6
Charge balancing of lithium-ion batteries.
Periodic Balancing Full Charge of lithium-ion batteries.
Charge Synchronization of lithium-ion batteries.
Add Hybrid Shifting and Peak Load Shifting functions on lithium-ion batteries.
Fix Wi-Fi disconnect problem. (only 13.10.0)
Add Auto Reconnect of Tools agent handler. (only 13.10.0)
Improve Start-up sequence on lithium-ion batteries.
SNMP v. 1.6
Dedicated and improved SOC calculation algorithm that always keeps track on SOC for Li-ion batteries, even if communication to BMS is lost. This improves robustness and makes sure that the Li-ion battery bank is charged at the right moment.
Dynamic float charge function that maximizes the life of the battery bank in cases where the battery bank remains fully charged for prolonged periods of time.
Improved pre-charge function that limits inrush currents that otherwise would have tripped battery breakers, a well-known problem for Li-ion battery banks.
New voltage control charge mode added to previous Static SOC mode, enabling more alternatives of desired charge/discharge behaviour.
Update to SNMP v. 1.5
New Green Power Influx feature, AC Power Minimization.
Add Tenant ID 0.
Temperature derating on Linux-CPU temperature.
Update to SNMP v. 1.4
Improved current limitation when communicate with lithium-ion batteries.
Add Event to Reset old alerts from eSite Tools.
Integration of Incell SLB48 lithium-ion.
Increase num. of integrated BMU,s from 12 to 16.
Improve alarm handling.
Update Shoto integration to Modbus register version 1.2.
Update modbus server register to 4.0.
Integration of Shoto SDA10-48100P lithium-Ion.
Automatic conversion of old custom battery files.
Fix time different between site and Tools server
Update manuals with appendix.
Fix modbus com error to genset AMF panels.
Remove dual chemistry function from Web GUI. Not supported any more.
Integration of Sacred Sun lithium battery
SNMP - Add read write support for v1/v2
Changes in Modbus-handler to support communication to battery and AMF panel at the same time. Remove Modbus over TCP support.
Add 3 more tenant-monitoring
eAgent - change name timezone and ambient temp in Tools
Change battery configuration web pages to use battery template.
Add 8 configurable digital inputs.
The function "Mixed Battery Chemistry is deprecated and will be deleted in future release.
eSite x10 can be provided with AC power supply from genset and grid and with DC power supply from solar arrays. The supplied power is used to support customer load and to charge a battery bank. The AC power supply is converted into -48 V DC through rectifiers in the Main Compartment. The DC power supply is converted into -48 V DC through solar converters in the Main Compartment. Switching between the connected power sources is automatic through the patented silicone controlled rectifier (SCR) functionality. eSite x10 sends start and stop commands to the genset(s) automatically when required. If solar arrays are installed, they are under regulation from the internal solar converters at all times and will supply power when the weather conditions are favourable.
The Main Compartment contains:
Rectifier x 3
Solar converter x 3
SCR (replaces standard ATS)
Current, voltage, frequency and temperature sensors
Wi-Fi
GSM
Main Controller
Caution
The Main Compartment must be connected to the Connection Compartment only, unless a written statement from eSite Power Systems permits other connectivity devices. No third party connection device can be used without explicit consent and approval by eSite Power Systems. The Connection Compartment and the power connectivity is subject to regulatory control by eSite Power Systems.
Figure 3.1 shows an overview of a mounted eSite x10 unit with the most important features identified as follows.
A Mounting Frame B Main Compartment including Lower Main C Product marking plate G Connection Compartment lid D Visual indication – green LED E Visual indication – red LED F Connection Compartment G Connection Compartment lid
Figure 3.2 shows an overview of a complete site setup with the eSite x10 and associated systems on site, identified as follows.
A eSite x10 B eSite Tools C Battery cabinet and battery bank D Solar panels E Grid F Genset G Customer load
The list below outlines the options that are referenced in this manual. For a complete description of options, compatibility between options and what is included in each option package, see eSite x10 Standard and options document.
Enables connection of a second AC source. Switch between sources with solid state electronics. Current, voltage and frequency is measured from both sources.
Include 6kW solar converters. Advanced Solar MPPT control, Green Power Influx
Genset management, Genset Night Silence function, Genset Exercise run, Battery Charge strategies (Voltage Cycle, Static-SOC, Partial-SOC), Battery Monitoring (SOC, Battery capacity), UPS AC mode, Configurable Modbus client (AMF panels)
Pressure-based fuel level sensor for monitoring fuel consumption and anti-theft control.
Individual DC output monitoring: 6 x Tenant current measurement sensor. Tenant identification and energy consumption analysis.
Modbus server, SNMP
FOTA (Firmware Over-the-Air) upgrades, Remote configuration (eSite Tools), Remote monitoring, Alarm/Error event to NOC, Report services, Diagnostic
Support for battery cabinet cooling equipment with Delta Ambient and Battery Temp Level control options
Full integration of two (2) eSite x10 units for double rectifier capacity
Support for two (2) additional solar controllers (any brand)
Some options/features may be received as additional s/w patches. This may apply for already existing features or new features developed and customized upon request, based on customer requirements in coordination with the eSite development team.
These options are normally disabled from the standard software implementation and are not visible in any UI.
Contact eSite Power Systems to get more information regarding custom specific options.
Full Li-ion integration (any brand), Battery Charge strategies (Lion)
Full integration (any brand)
Copyright © 2021 eSite Power Systems AB
eSite x10 uses the following power source priority order:
Solar power
Grid power
Genset power
If solar or grid is not available, the genset automatically starts when the batteries must be charged. If grid becomes available during a genset charge, the genset is stopped. Only one AC source can be active at the time. If solar power becomes sufficient, this can also stop the genset, utilizing the Green Power Influx feature. If solar power is available at the same time as grid or genset power is available, solar power is always prioritized and maximized.
The Main Compartment converts the AC supply via three rectifiers into -48 V DC. The rectifiers provide 3.5 kW per unit, for a total of 10.5 kW. The inputs from the AC sources are continuously measured to ensure that the most efficient AC source is used. The switching between the connected AC sources (gensets/grid) is automatic.
The eSite x10 patented Silicon Controlled Rectifier (SCR) is designed to improve the performance of the system compared to a traditional Automatic Transfer Switch (ATS). Both an ATS and SCR allows for switching between two AC sources, but while the ATS is based on mechanical switching, the SCR uses power semiconductors.
One or two (optional) AC sources can be configured in the eSite Web interface. The options are No Source, AC Genset 1 and 2 and Grid.
The eSite x10 can be in 4 different system modes: 'Auto', 'Auto Full Charge', 'Manual' and 'Safe Mode'.
Auto mode is the normal mode the system operates in. The eSite x10 is working automatically with no user interference and controls all features and external command signals.
Auto full charge mode is activated when the batteries need to do a Full Charge cycle.
The following conditions activate a full charge:
One of the Load Voltage Disconnect (LVD) breakers has tripped.
The time interval between two Full Charge cycles has elapsed. This parameter can be changed in local web configuration.
The battery Energy throughput has reached its limit value. This parameter can be changed in local web configuration.
See section Full charge cycles
Manual mode is activated when a controlled AC source, typically a genset, is manually forced on or off. This can be done from the local web pages or remotely via eSite Tools.
In Manual mode normal functionalities, including power prioritizing and automatic external commands, are overridden. Manual mode is exited when all AC source controls are set to Auto.
Safe mode is activated when the battery MCB is tripped or if eSite x10 cannot determine the correct state of the battery bank. For example: If one or both of the battery voltage or current sensors have failed, the eSite x10 will enter Safe mode.
For the case when no battery MCBs are present and configured as “No Input”, Safe Mode is activated by the following conditions:
Voltage sensor mismatch alarm is active (system and battery voltage sensors differ by > 1V)
System and battery voltage sensors are valid
Genset is running and gives feedback
No battery charge current detected (measured value less than configurable threshold, default 2 A)
These conditions combined indicate that no battery bank is present and eSite x10 will enter Safe Mode. This applies for lead-acid batteries only.
When Safe mode is active, the voltage levels and the maximum battery charge current are reduced and the genset is commanded to continue running.
eSite x10 supports usage of two different types of battery chemistry : lead-acid batteries and lithium-ion (Li-ion) batteries. Several different brands, models and sizes of batteries have premade configurations that simplifies site commissioning and operation. New premade configurations can be created upon request. The battery parameters are also possible to set individually through several interfaces (e.g. eSite Web, eSite Tools, SNMP) in order to support new battery types and to improve performance.
Traditionally, conventional lead-acid batteries has been the main choice for hybrid operation on remote sites. They are attractive for a wide variety of usage due to being of relatively low cost, having a long life-time and high reliability, but they also come with drawbacks including the need for temperature compensation and bulky storage, especially for high-capacity banks.
Use of up to two (2) battery banks is supported, each with a separate charge current measurement sensor. This option is called Dual battery bank.
Two different set voltage levels are used when charging lead-acid batteries: Boost voltage and Float voltage.
Boost voltage is higher than float voltage and is used to improve the charge performance. However, batteries kept at boost voltage for longer periods of time eventually take damage. Float voltage is lower and is used for long periods of continuous available AC power, for example when Grid is present for a long time.
The following battery states are defined for lead-acid batteries. The states indicate at what stage in the charge cycle the battery bank is. The battery state information is available on eSite Web. If Dual battery banks are installed, the battery state is considered to be the same for both battery banks.
Discharge: The discharge state is entered when current is drawn from the batteries and the voltage is decreasing.
Charge: Charging occurs when either eSite x10 rectifiers or solar converters are delivering constant charging current to the batteries.
Absorb: Absorb is a charging state where the charging voltage is limited by the rectifiers or solar converters. The charging voltage has an optional temperature compensation feature. When in the Absorb state the battery bank is charged at constant voltage.
Equalized: Equalized is an extended constant voltage charging mode to help eliminate soft sulfation in lead-acid batteries. The voltage level is adjustable.
Fully Charged: In the Fully Charged state, the batteries are considered to be fully charged. The battery bank will remain in this state until SOC has dropped 5 % since the fully charged state was entered.
eSite x10 offers four battery charge strategies to optimize the use of the lead-acid battery bank used on site. Battery charge parameters can be viewed on eSite Web under the Battery menu.
Voltage control
The battery bank starts to charge at specified voltage levels. The charging stops when a specified voltage level is reached and the charge current falls below a specified value. The method does not take into account the state of charge.
Used with a basic battery bank. The use of batteries is not optimized. The life-time of the battery bank is relatively short.
Static state of charge (SSOC)
The batteries start and stop charging at predefined levels of the state of charge. The SOC values for starting and stopping charge cycles is dependent on battery configuration and can be changed in the local web pages.
Used with battery bank delivered with proper data. SSOC gives a good estimation of the battery life-time. This method is convenient for a very remote site were it takes a great effort to switch battery bank.
Partial state of charge (PSOC)
The batteries are charged up until the charging performance decreases, based on the charge acceptance of the battery. When the charge current has decreased below a specified threshold the normal charge cycle is finished. The SOC level when this occurs minus a SOC window, default 30 %, decides when the next charge cycle starts. SOC level when the normal charge cycle is finished depends on several factors.
Used with battery bank delivered with proper data. Partial state of charge saves fuel costs and is the most cost saving strategy. The life-time of the battery bank may be shorter than if the SSOC strategy is used. The batteries are charged with low current as it is fuel inefficient when the batteries have a poor charge acceptance. As the genset runs more efficiently at higher output power compared to when it is running at idle or has low output power, the frequency of genset maintenance is also lowered. Thus, PSOC is a fuel efficient option.
UPS AC mode
This is a special mode where the batteries are not cycled and AC power is not turned off when the batteries are fully charged. The AC power can be either Grid or genset.
A Full Charge cycle is a longer charge cycle that charges the batteries to the maximum available capacity. Periodic use of the Full Charge cycle is needed to maintain the health of the battery bank, balance battery banks/strings and to “recalibrate” the state of charge. A Full Charge cycle charges the batteries at boost voltage until the battery is in the Fully Charged state. A Full Charge cycle can be triggered manually, for example during site commissioning, or by one of these three threshold values:
Time interval
Energy throughput
Low voltage, used on Static SOC and Partial SOC charge strategies
An Extended Full Charge cycle is triggered when the battery voltage has fallen so low that both HP and LP LVD are activated. An extended full charge cycle prolongs the Full Charge cycle with an extra timer, default set to 18 hours. This is an effort to recover the battery bank from any damages caused by the low voltage. An Extended Full Charge cycle can also be triggered manually.
The battery charge mode indicate what type of battery management that is currently active. The charge mode is independent of the selected charge strategy and gives information about whether the battery bank is subjected to normal charge cycling or if a scenario that overrides these settings is active, such as when a Full Charge cycle is triggered.
The active charge mode is presented under the Battery tab on eSite Web and in eSite Tools.
For handling of lead-acid batteries, one of the following charge modes is used.
Normal Charge: Standard hybrid operation is active. The battery bank is charged/discharged according to the selected charge strategy and its associated control parameters.
Full Charge: A Full Charge cycle has been triggered and is active.
Extended Full Charge: An Extended Full Charge cycle has been triggered and is active.
Safe Mode: eSite x10 is currently in Safe Mode and cannot determine the correct state of the battery bank. Maximum allowed charge current and set voltages are lowered to protect the system.
The temperature is of great importance regarding the health of lead-acid batteries. The temperature information is used to adjust the voltage level when the batteries are charged. At high temperatures, the batteries are charged at a lower voltage level and at low temperatures batteries are charged at a higher voltage level. This temperature compensation can be configured.
The battery temperature sensor is placed in the centre of the battery bank (see figure 8.1) and connected to the eSite x10.
eSite x10 continuously ensures that the battery max charge current is not exceeded. This threshold value for current limitation is configurable. The battery charge current is measured in the Main Compartment. A positive current indicates that the batteries are being charged. A negative current indicates that the batteries are being discharged.
An increasingly popular alternative to lead-acid batteries for powering remote sites together with the eSite x10 is Li-ion batteries.
Due to their superior power density and sophisticated module designs, including the possibility of external communication, Li-ion batteries make for effective storage solutions of high capacity, combined with intelligent monitoring and managing, albeit at a slightly higher cost and a higher sensitivity to overcharging/overdischarging.
All commercial Li-ion battery modules relevant for this application are equipped with internal electronic protection, cell balancing circuits and supervision/alarm circuits.
eSite x10 is capable of managing a Li-ion battery bank of up to 16 installed BMUs connected in parallel. If a communication cable is mounted between the battery bank and the eSite x10, all alarms and important data (e.g. Voltage, SOC, Current) from the modules are logged, presented on the local web site and sent to eSite Tools. For operation without communication, or when communication is lost, this data is either measured or calculated by dedicated estimation algorithms based upon the available information about the battery type and the size of the battery bank.
eSite x10 ensures that charging voltage levels and maximum current stays within the limits according to the battery specifications. Maximum charge current is automatically adjusted depending on how many modules are connected or if any battery fuses are tripped.
Li-ion batteries from the following manufacturers are currently integrated with eSite x10. Contact eSite Power Systems for information regarding models and version.
LG Chem
Sacred Sun
SAFT
Shoto
Vision
Polarium (previously Incell)
See the Appendix, section Installation and configuration of lithium-ion battery for more information.
When charging Li-ion batteries, a configurable set voltage level is used. For long periods of operation with available AC power, the set voltage is ramped down to a lower level to preserve the health of the battery bank.
These voltage levels are individual for each power source and may be preconfigured upon delivery. Normally, they are provided by the battery manufacturer.
The following battery states are defined for Li-ion batteries. The battery state information is presented on eSite Web and in eSite Tools. For Li-ion configurations, all BMUs connected in parallel will be considered as one battery bank.
Precharge: Precharge is the initial state of the battery state algorithm. In Precharge, the system takes necessary precautions to stop inrush currents from going into the battery bank by slowly ramping up the system voltage from a low starting point until the battery voltage is matched. When current is detected going in or out of the battery bank, the Precharge state is exited.
Discharge: The discharge state is entered when current is drawn from the batteries and the voltage is decreasing.
Charge: The Charge state indicates that either the eSite x10 rectifiers or solar converters deliver enough current to charge the batteries.
Fully Charged: In the Fully Charged state, the batteries have met the manufacturer specifications for being considered fully charged and will not accept further charging. This state is exited when the SOC has decreased by 1 % since the Fully Charged state was entered.
Equilibrium State During equilibrium, no current flows in or out of the battery. This state is exited as soon as current going in or out of the battery bank is detected.
eSite x10 currently offers two charge strategies to optimize the use of a lithium-ion battery bank on site: Voltage Control (VC) and Static SOC (SSOC). Battery charge parameters can be viewed on eSite Web under the Battery menu
The VC strategy works very similarly to the corresponding lead-acid strategy, see section Lead-acid batteries. Operation will be based on the overall measured battery voltage. This strategy is well suited for site setups with no battery communication or when SOC shall not be considered.
The static SOC strategy starts and stops charging based on configured Start SOC and Stop SOC levels. This is arguably the best adapted strategy for Li-ion battery banks with active communication to the eSite x10. The strategy offers several options to control the cycling based on the reported BMU data that are configurable via the Static SOC Control Options parameter. The options are
Average SOC - A charge cycle will start and stop when the average calculated SOC of the battery bank reaches the start/stop thresholds.
Protective SSOC - Start/stop on Min/Max BMU SOC value. A charge cycle will start when the minimum reported BMU SOC value reaches the Start SOC threshold and stop when the maximum reported BMU SOC value reaches the Stop SOC threshold. This behaviour will prevent overcharging and overdischarging of any single BMU in the bank.
Balancing SSOC - Start/stop on Min/Min SOC value. A charge cycle will start when the minimum reported BMU SOC value reaches the Start SOC threshold and stop when the minimum reported BMU SOC value reaches the Stop SOC threshold. This behaviour will ensure that all BMUs are charged up to the desired SOC .
Options 2 and 3 require active communication with the battery bank. In setups with no communication or if communication is lost, the SSOC strategy will be based on the calculated average SOC value for the entire battery bank regardless of the selected option.
Voltage control
The battery bank starts to charge at specified voltage levels. The charging stops when a specified voltage level is reached and the charge current falls below a specified value. The method does not take into account the state of charge.
Used in applications where no communication is available or when SOC is not of interest. The use of batteries is not optimized.
Static state of charge
The batteries start and stop charging at predefined SOC levels. The SOC values for starting and stopping charge cycles are configurable and can be changed in the local web pages.
Used with battery bank delivered with proper data. Static SOC gives a good estimation of battery life-time. Use of batteries is optimized with data from the internal BMS of the batteries.
For battery banks with apparent propagating unbalance during charge cycles, a synchronization step at the end of each charge cycle can be enabled, where the BMUs are allowed to synchronize internally under a period of no or very low charge current. This final balancing touch is best performed while charging at the top of the charge cycle when internal voltage differences in the bank are more apparent and internal cell resistances are minimized. The charge current limit and the duration of this period are both configurable.
As a complement to regular charge cycles in hybrid operation for Li-ion batteries, optional full charge cycles, here labelled Balancing Full Charge cycles, are supported by eSite x10. They are slightly different from the Full Charge cycles used for lead-acid batteries, where maintained charge current for long periods of time is necessary for ensuring good battery performance. Li-ion batteries are less sensitive to damage from partially charging the battery bank than lead-acid batteries, and do not have the same need to repeatedly be fully charged. Indeed, it can be argued that fully charging Li-ion batteries to a large extent should be avoided in order to not risk overcharging the batteries, which may cause damage. However, for a newly installed or a severely unbalanced battery bank, it might be necessary to perform a full charge cycle to reach the very top of the battery voltage/SOC characteristic and achieve appropriate balance within the bank.
Balancing Full Charge cycles are available, and will work in the same way, for both the Li-ion VC and SSOC strategies. For the SSOC strategy, a configurable safety voltage level has been introduced that will trigger a Balancing Full Charge cycle in any faulty scenario where the SOC cannot be reported or calculated correctly. This voltage level should be set to a higher value than the LP load LVD voltage level as a precaution to prevent LVD.
A Balancing Full Charge cycle can also be triggered manually via a command from the eSite Web Battery tab.
If desired, periodic Balancing Full Charge cycles may be enabled. When enabled, Balancing Full Charge cycles will be triggered automatically based on intervals of either accumulated energy throughput from the battery bank or number of completed regular charge cycles, whichever occurs first. Both interval parameters are configurable.
A Balancing Full Charge cycle is completed when the battery voltage has exceeded the BMS Fully charged voltage level and the charge current has fallen below the battery cut-off level specified by the manufacturer. After a Balancing Full Charge cycle is completed, it is followed by a mandatory Synchronize step before AC power is turned off. Upon completion, the periodic intervals for energy throughput and number or cycles are both reset.
The active charge mode is presented under the Battery tab on eSite Web and in eSite Tools.
For handling of Li-ion batteries, one of the following charge modes is used.
Ramp Up: The battery bank is in the Precharge state and the system is slowly ramping up the voltage to avoid initial inrush currents.
Normal Charge: Normal hybrid operation is active. The battery bank is charged/discharged according to the selected charge strategy.
Synchronize: Synchronization of the BMUs in the battery bank is active. The battery bank is forced into the Equilibrium state and is not charged/discharged.
Balancing Full Charge: The battery bank is currently being charged in a Balancing Full Charge cycle. The system will be in Auto Full Charge mode.
Safe Mode: eSite x10 is currently in Safe Mode and cannot determine the correct state of the battery bank. Maximum allowed charge current and set voltages are lowered to protect the system.
The purpose of Hybrid Shifting (HS) is to increase solar production efficiency on hybrid sites during the day by having a lower SOC in the morning and thus have more solar energy captured in the batteries. The simple concept of hybrid shifting is to split a day into 2 periods where the DG stop voltage differs.
Example:
3:00-09:00
54.0V
09:00-2:59
56.5V
The configurable parameters can be set via local Web, eSite Tools and SNMP. See Battery section for details how to configure the feature.
The purpose of Peak Load Shifting (PLS) is to maximize the solar energy for on-grid sites where the grid is available and stable. The idea behind the feature is to:
Power the site load and if possible, charge the Li-ion battery bank during daytime from the solar panels.
At a configurable time (PLS_end_time) the grid should be used to charge the battery bank to adjustable Vmax (normally set to float voltage) at full power.
During the night, the grid will be used to power the load and keep the battery bank at Vmax, normally at float voltage.
At a predetermined and configurable time (PLS_start_time), the AC rectification should be inhibited, and the battery bank will power the load until the battery bank voltage has reached an adjustable voltage setpoint (PLS_Voltage).
Grid will maintain the battery bank at a predetermined voltage level(PLS_Voltage) if solar power is not sufficient to carry the site load.
If grid becomes unavailable and battery bank reaches the DG start voltage, the genset will start. At this point, PLS functionality will be suspended and Hybrid Shifting will take over until the batteries reach the DG stop voltage and until DG is turned off again.
Example:
3:00-09:00
54.0V
09:00-2:59
56.5V
The configuration parameters can be set via local Web, eSite Tools and SNMP. See Battery section for details how to configure the feature.
Below graphs shows the different power sources and different event scenarios.
Normal operation 1
During nighttime grid powers the load and SOC/Vbatt is maintained at Vmax. At PLS_start_time, grid power is switched off and battery discharges until PLS_Voltage has been reached. At this time, grid will power the load again and solar will charge battery bank if solar power is above load power. If solar power is below load power, grid will support so that SOC/Vbatt is kept at PLS_Voltage (Solar power + grid power = load power). At PLS_end_time grid will charge the battery bank until Vmax has been reached.
Normal operation 2
During nighttime grid powers the load and SOC/Vbatt is maintained at Vmax. At PLS_start_time, grid power is switched off and battery discharges until time PLS_Voltage has been reached and grid will power the load to keep SOC/Vbatt at PLS_Voltage. Solar will charge the battery bank if the solar power is above the load power. If the solar power is below the load power, grid will support so that SOC/Vbatt is kept at PLS_Voltage (Solar power + grid power = load power). At PLS_end_time, grid will charge the battery bank until Vmax has been reached.
Grid lost during daytime
In this scenario grid is lost during daytime and system reverts to Hybrid shifting mode instead. When grid is lost, SOC/Vbatt will drop until DG start is reached. The Genset will charge the battery bank but since the time is past Time HS1 (Hybrid Shifting time 1), Genset will charge the bank until DG stop HS1 has been reached. At sunset, the SOChas again dropped to DG start but, in this case, the Genset will charge the battery bank up to DG stop HS2 since time has passed Time HS2.
Grid lost during Genset charging
In scenario 4, grid is lost in the morning and the system reverts to Hybrid shifting mode instead. When grid is lost, SOC/Vbatt will drop until DG start is reached. The Genset will charge the battery bank but during charge, grid becomes available again and eSite x10 will shift to Grid and finalize the charge sequence until DG Stop HS1 has been reached (since time has passed Time HS1). When charge cycle has been completed, PLS mode will become active again.
Read
Always follow the genset manufacturer's instructions during work with the genset.
eSite x10 automatically starts and stops the genset when requested by the selected battery charge strategy, voltage level or set time. The genset start signal is controlled by a relay that is closed when eSite requires the genset to start. The output relay can be configurable via the local eSite Web.
eSite x10 determines the genset power request and controls the genset power output so that it is not overloaded. This can be used to prevent overload on smaller gensets.
Ready. Genset is ready to start, waiting for a charge request.
Start request. Genset is requested to start. It stays in this mode until eSite sense voltage.
Warm up. Warming up genset without any power request.
Ramp up. The requested power is linearly ramping up.
Running. Genset is providing power.
Ramp down. Genset is ramping down.
Cool down. Genset is running in idle without any power output.
Off state. Waiting for the genset to turn off. The state is active until the genset has stopped or 5 min has passed.
The times for genset warm up, ramp up/down and cool-down can be configured.
Dry contacts. eSite x10 has 3 available input relays for each genset, when triggered an alarm activates. The input relays can be configured as normally open, normally closed or not used.
Modbus. eSite x10 can communicate with the genset to read signals and alarms directly from the genset AMF panel. The supported protocol is Modbus-RTU. Configuration for different genset panels can be customized on site or a premade configuration set can be created upon request. The data and alarms that are retrieved from the genset panel are stored and logged, both locally and remotely, every 10 minutes.
eSite x10 supports operation with two connected gensets. Only one genset at a time can deliver power to the system. In regular hybrid operation, eSite x10 alternates the charge cycles between the two gensets. If one genset fails during operation, the other genset is immediately commanded to start.
For example:
Genset 1 fails during a charge cycle.
The start command to genset 1 stops. Genset 2 is commanded to start and completes the charge cycle.
Next charge cycle starts with genset 1. If genset 1 does not start, genset 2 will be commanded to start.
eSite x10 can keep track of the total runtime and the remaining time (hours) until genset service is required. The service interval and when the alarm is triggered can be configured. Total runtime can be reset manually.
When Static SOC or Partial SOC charge strategy is selected, eSite x10 estimates the time until the genset starts to operate. The estimation is based on the discharge current and the low SOC threshold level where the charge cycle starts.
Caution
Night Silence mode prevents the genset from running at night. This can have a negative impact on battery health and site performance and void the battery warranties.
The Night Silence period start time can be configured. eSite x10 can pre-charge the battery bank to ensure that it is sufficiently charged when the Night Silence period starts. The end of the period can be configured to end by time, voltage or SOC, whichever occurs first. Outside the period the configured charge strategy is used.
Night Silence mode is used for both off- and on grid sites. For on grid sites pre-charge is usually not required. If the grid fails during the silent period the configuration determines when the genset is allowed to start.
When Night Silence is inactive or disabled, charge cycles are performed without interference.
The Night Silence pre-charge function charges the battery bank to a state where its autonomy time fulfils the Night Silence period. The function calculates the required number of ampere-hours (Ah) required for battery autonomy time based on the present site load and the number of hours of the silence period.
The following formula is the estimate of the preceding charge time in hours where Autonomy Ampere Hours is the needed energy required by the batteries for the duration of the Night Silence period. Safety margin is a configured threshold for the energy level that battery bank should be at in the end of the period. Present battery capacity is the capacity of the battery dynamically calculated, and the max charge current is the max allowed charge current.
For Night Silence to accurately shut off the genset at the configured time the site utilizes Network Time Protocol (NTP) time synchronization or is synchronized from eSite Tools. A local time zone must be configured at each site.
During the active period the genset is not commanded to start. The tenant receives power as long as the Low Voltage Disconnect is not triggered. The configurations are usually set for the active period to be aborted before this happens. To manually force the genset to start overrides the Night Silence and allows the genset to start.
The Night Silence period can be stopped before the stop time is reached to allow the genset to start.
If the stop on charge request configuration is ON, Night Silence is stopped when a charge request is triggered by the charge strategy. This configuration is usually used when the pre-charge cycle is desired to prepare the batteries for the night but standard charge strategy still is used.
A charge request always starts the genset if grid or solar is not available. A full charge cycle triggered by time or energy is postponed until the end of the Night Silence period. A full charge cycle not triggered by time or energy aborts the Night Silence period regardless if it was triggered during or before the Night Silence period.
If stop on charge request is OFF, the Night Silence period is aborted by a voltage level or a SoC level, whichever occurs first. A deeper discharge than intended by the charge strategy can be achieved to prolong the silent period. The values can be set below the Low Voltage Disconnect threshold.
Three (3) internal solar converters and two (2) external solar converters can be utilized by the eSite x10. The internal solar converters require no configuration and use an MPPT (maximum power point tracking) technology to ensure that the harvested solar power is maximized continuously. Any external solar converters must be separately connected and enabled in configurations.
If the solar array is incorrectly connected, for example with reversed polarity, an alarm becomes active and a relay disconnects the solar array to protect the eSite x10 system.
The eSite x10 internal solar converters are designed for use with mono-crystalline and polycrystalline solar panels with 72 cells and 6 inch wafers. An optimal solar array is easily configured with these types of panels. It is also possible to use panels with other number of cells.
Caution
Do not connect solar panels with built-in electronics to eSite x10. Contact eSite Power Systems for further information regarding this.
Open circuit voltage of each string of solar panels must never exceed 140 V.
The total of solar array current never exceeds 20 A per solar converter. Additional panels are not harmful to the eSite x10, but might not be utilized optimally.
The Green Power Influx (GPI) component maximizes solar energy harvesting in relation to other power sources. When sufficient solar power is available, GPI becomes active and power drawn from the genset(s) and grid is inhibited.
Activation of the GPI functionality depends on the following conditions:
Green Power mode must be enabled.
Solar Power is sufficient.
Battery state of charge (SOC) is sufficient.
Batteries are in Normal charge mode and voltage is above limit.
System voltage is above limit.
Specified time interval (if applied).
Solar power is sufficient when it holds a configurable percentage of the load. To avoid frequent start and stop of the genset in case the solar power fluctuates, a delay timer for entering and exiting GPI is used to make sure that the solar power is sufficient and stable. This delay timer can be configured.
To ensure that the backup time is sufficient in case of a genset or Grid failure, the battery bank must be above certain SOC and voltage threshold levels before GPI is activated. These thresholds are configurable, see Solar section for details how to configure the feature.
The GPI function is always in one of the following states:
Disabled. GPI is disabled (default)
Inactive. GPI is enabled by the user, but the solar power is insufficient or eSite x10 is currently in Safe mode.
Stopped. Solar power is sufficient, but the battery voltage or SOC is too low.
Idle. The solar power has not reached the selected load percent activation level (Load Percent operational mode), or current time is outside the selected time interval (Time Interval operational mode).
Active. All conditions are fulfilled, genset(s) and Grid are inhibited and the Solar power is fully utilized.
Green Power Influx has three (3) operational modes to choose from when activated: Load Percent operational mode (default) see section "Load Percent operational mode", Time Interval operational mode section "Time Interval operational mode" and "Maximum Solar Power in Good Grid (AC Power Minimization)"
Load Percent operational mode is the default mode for GPI. This mode is suitable for all AC source configurations and when active, it inhibits both Grid and genset from running.
In Load Percent operational mode, GPI is activated and the AC sources are switched off at a predetermined percentage of Solar power with respect to the customer load. AC power remains inhibited as long as the Solar power is sufficient. When the Solar power drops to a certain percentage level of the customer load, GPI is deactivated and AC power is allowed again to continue charging of the batteries.
If a genset is connected to the eSite x10, an example of a typical GPI application scenario is given in the next figure.
For the example above, the Solar Load activation threshold is set to 80 % of the customer load and the deactivation threshold is set to 70 % of the customer load. If the Grid is the primary AC source, the GPI component switches off and reengages the grid at predetermined percentage levels of solar power with respect to the customer load.
In Time Interval operational mode, specified times are set to enable/disable the AC source(s) according to when the Solar power is expected to be sufficient to run the customer load. The start/stop times of this function are configurable.
The Time Interval operational mode is mainly intended for use on sites with reliable Grid connections and high Solar output during daytime. When the purpose is to disable the genset from running in a specified time interval, it is recommended to use the Night Silence function instead.
Thus, in a typical application scenario for an on-grid site with good Grid quality, the customer can choose a disable time where the Grid should be disabled and an enable time for the site to re-enable the Grid. An example is given in the next figure.
This time interval example shows a Grid disable time at 05:00 and a re-enable time at 18:30.
This feature covers the need to minimize the energy used from the Grid on telecom sites where there is a substantial amount of installed Solar power, and hence maximize the use of installed Solar power capacity.
The aim is to use as much Solar energy as possible during the daytime to support both the telecom load and at the same time charge the battery bank. To be able to partly charge the bank, this feature is preferably applicable to Li-ion battery banks.
Power the site load and charge the Li-ion battery during daytime via the solar panels.
Power the site load by the battery bank when there is no solar available.
If the battery bank has reached a low predetermined SOC level (called SOCmin) during night, the grid will be used to power the telecom load only.
If the Grid becomes unavailable, the genset will be used to power the load.
Normal Operation
The battery bank will power the load after sunset and when the SOC has reached the SOCmin, the grid must supply the load during a portion of the nighttime. There is a load decrease/increase during night and hence power from grid will follow accordingly. SOC is maintained at SOCmin during night.
Grid loss during night
In this scenario, the grid is lost during night and the genset will be started to power the load until the solar power is enough to carry the telecom load.
Both grid and genset lost during night
The grid is lost during night and the genset fails to start after several start attempts. SOC will drop to SOClvd level and the eSite x10 will do a low voltage disconnect, hence dropping loads. Note that this will be in two steps, first disconnect of low priority load and later high priority load, this is not shown in the graph.
The telecom load will be lost until the grid is available again. Grid will be used at maximum power to charge the battery bank up to SOCmin level and then be lowered to just power the load and keeping SOC level at SOCmin until the solar power can power the telecom load.
Note that if the genset suddenly is operational again during low voltage disconnect, maximum power will be used from genset in order to bring the SOC up to SOCmin level.
Solar power only
In this case, solar can power the load without use of AC power.
In addition to the capacity of the internal solar converters, the eSite x10 supports a maximum of two (2) external solar converters that can be connected to the system. External solar converters operate independently and are not controlled by the eSite x10 system. A current sensor must be connected to each external converter to measure the added current to the system. The added current is taken into consideration by the eSite x10 in its regulation of internal converters. The CAN connected sensors are configured in the Solar web pages. Contact eSite Power systems for detailed installation instructions.
Grid control is the collection of settings that monitors and manages the power extraction of a connected grid. Depending on the quality of the grid, the system uses different modes of operation for optimal performance. The system is designed for a three-phase grid connection, but is also capable of handling single phase connections.
Each rectifier measures voltage and frequency independently. If a phase is invalid, the other rectifiers continues to operate with the valid phases. A phase is valid inside these ranges:
Voltage active range 85 – 300 Hz.
Frequency active range 45 – 65 Hz.
Outside these ranges, the rectifiers are disabled.
The performance of the rectifiers is monitored and presented as Grid status:
Invalid. All rectifiers are disabled due to insufficient phase voltage and/or frequency. Grid is not available.
Inhibited. Grid is available on at least one phase, but all rectifiers are inhibited from running and no power from grid is extracted. This state is entered when GPI is active or when the genset is prioritized to run, e.g. with an active Exercise Run request or when the genset is forced on.
Partial. One or two phases are valid, the rectifiers are active and running. Grid is partially available.
Ok. All three phases are valid, the rectifiers are active and running. Grid is available.
Power extraction from grid is limited by the size of the grid fuse. This value can be configured to ensure the fuse is not tripped and overloaded. Power extraction also adapts to the available grid voltage and classifies the quality of the grid according to the following:
No grid (< 85 V)
Bad grid (85 – 200 V)
Good grid (> 200 V)
Good Grid
In Good grid mode, the rectifier is requested to extract the maximum possible power, 3 500 W, from the grid. The maximum possible power can be configured.
If the grid is of low quality, set a lower grid fuse rating.
When entering Good grid mode from Bad grid mode, the rectifier rapidly ramps up the current to the maximum level.
Bad Grid
If the grid is active but the voltage is less than the Good grid threshold (200 V), the grid is considered bad. The rectifier power extraction employs a dynamic strategy to extract power from the grid, with the aim of finding a stable state where the maximum possible power is extracted. The software sets the rectifier current, and thereby the power request, based on the grid voltage at any given time, continuously running the following steps:
If the grid voltage increases or remains unchanged, the rectifier current, and thereby the power request, is increased in small increments.
If the voltage decreases, the current is also decreased for stabilization purposes.
This process is active until the rectifier finds a stable point where the maximum power is extracted for the given voltage or until the grid enters Good grid mode.
As an alternative to regular hybrid operation, the eSite x10 can be set into an 'uninterruptible power supply' (UPS) state, where AC power is being utilized constantly. The main purpose of the UPS AC mode is to always keep the site on-line and the batteries fully charged. This application is mainly intended for use on sites with poor-quality batteries that cannot be relied upon to carry the customer load for any for any length of time. The battery bank will always be in the Charge state regardless of SOC and charge current, and will normally be kept at float voltage. Periodic or singular Full Charge cycles at boost voltage can be activated via configuration.
For site configurations with one AC source, i.e. a single genset or grid only, activation of this feature simply means that the available AC source will always be commanded to deliver power to the site.
As in normal hybrid operation, DC solar power may be utilized at all times in conjunction with the AC source(s). However, the Green Power Influx and Genset Night Silence features are not compatible with UPS AC mode and shall be disabled.
For grid/genset site configurations, AC power from either grid or genset may be utilized in UPS AC mode, with grid having higher priority than the genset. If one AC source fails, the second source is immediately commanded to start delivering power to the site.
For dual genset site configurations, equal run time of the two gensets is achieved by regularly switching between the gensets based on a timer. Both gensets are requested to run before switching source to ensure minimum downtime. If one genset fails while running, an alarm is triggered and a start request to the second genset is commanded. The time to detect malfunction and activate the alarm is configurable with the "Genset start alarm delay time" parameter. See section Genset configuration for more information.
All UPS AC mode configuration parameters have to be set in order to activate UPS AC mode, see section Battery configuration.
The eSite x10 is equipped with dual Load Disconnect breakers that are controlled automatically. This makes it possible to divide the customer load into two parts of different priority, a low priority (LP) part and a high priority (HP) part. In any faulty scenario where the system due to a major malfunction, such as the AC genset not being able to start, is unable to properly support the load and charge the battery bank, the system is eventually protected by tripping the breakers, disconnecting the load.
In such a scenario, the low priority (LP) customer load may be chosen to disconnect before the high priority (HP) load. The HP load is generally intended to be of smaller size than the LP load. Check the data sheet for current limitations of HP and LP loads.
This functionality is designed to keep the site online for as long as possible and to protect the health of the batteries.
The customer load is disconnected if incoming power is unavailable and the battery voltage falls below a configurable voltage threshold for a specified time (also configurable).
By disconnecting the customer load at low voltage levels, the battery bank is prevented from completely discharging. However, the delay timer makes it possible to handle sudden voltage drops upon engaging loads, i.e. if a load is engaged and the voltage drops below the defined threshold.
All LVD parameters are configurable, see section Low voltage disconnect settings.
When the system voltage falls below the threshold Low Prio load disconnect volt , the LP load will be disconnected after a Low Prio load disconnect time . An alarm for LP load LVD will be triggered.
When incoming power is available again, the battery voltage recovers to the Low Prio load reconnect volt threshold and the total delivered current exceeds the Low Prio load reconnect current threshold (default 20 A), a timer will start and the load will be reconnected after a short Low Prio load reconnect time .
For a quick recovery with a rapid increase to high voltage levels, the load may also be reconnected when the battery voltage exceeds the Low Prio load fast reconnect load . threshold without any delay.
HP load LVD functionality is disabled by default, but can be enabled with the High Prio load LVD enable setting. When this functionality is enabled, separate LVD settings (also configurable) for the HP load will be used.
If HP load LVD is disabled, the HP load will be disconnected and reconnected with the same settings as for the LP load LVD.
If HP load functionality is enabled and the HP load gets disconnected before the LP load, e.g. in case of a rapid voltage decrease, this will also trigger an LP load disconnect. Typically, the HP LVD has a lower voltage disconnect level but a shorter disconnect time. This will prevent the LP load from continuing to discharge the batteries.
The LVD breakers are protected by an internal system function that disconnects the load if the LP or HP current exceeds 200 A. If this occurs, an Alarm is also triggered. The system will automatically try to reconnect the load 5 times with 20 second intervals.
If the system does not succeed to reconnect, there is a Reset Load switch button on the eSite Eeb pages. Pressing this button will reset the LVD breakers and reconnect the load. It is also possible to undock the main compartment to reset the LVD breakers.
The eSite x10 supports monitoring of up to six (6) tenants separately. The total consumed load, including both HP and LP loads, is measured and logged. Auxiliary equipment on site is not included.
The sensors shall be connected via CAN, see detailed info in the Tenant Configurations.
eSite x10 has a feature able to control, i.e. turn on/off, an external cooling device connected to a digital output port. The device is controlled with a relay based on the readings from the temperature sensors.
This feature can be used to control the temperature in the battery cabinet to further extend the battery lifetime in areas where appropriate battery temperature is not guaranteed by the site environmental conditions.
The Ambient temperature sensor and the Battery temperature sensors are both required by the Cabinet Cooling feature. If any of the sensors becomes invalid while the feature is activated, the feature will be in "Fallback" mode and the output will be ON.
The Digital output relay shall be configured to one of the standard output relays on the I/O board. See the I/O Configuration page.
The feature can be set into two different modes: Delta Ambient mode, which is based on the temperature difference between the battery and ambient temperatures, and Battery Temperature mode, which uses absolute temperature levels to start/stop cooling.
All configurations can be done in local web pages, see Cabinet Cooling setup.
The Fuel Monitoring functionality gives the customer detailed information about the fuel level, consumption and abnormal events. Volume level, consumed, filled and lost volume is tracked and logged. The fuel monitoring makes it easier to plan when to refill fuel.
The fuel monitoring sensor is connected to the analogue input 0 – 10 V and receives power from the 24 V output. Two fuel sensors can be connected at the same time in order to monitor two separate tanks.
Filled and lost volume is calculated when a volume change has been detected. A volume change is triggered when the volume changes rapidly. This is configured as a percentage of the total tank volume / time span. Default is 4 % / 30 min.
The thresholds for low and very low fuel level alarms are configurable. Sensor out of range alarm is triggered when the voltage output of the sensor is outside its configured range.
Connect fuel sensor 1 to Analogue in 2+ and Analogue in 2- Connect fuel sensor 2 to Analogue in 3+ and Analogue in 3-
A Modbus server can be started via the local eSite Web configurations. eSite x10 support Modbus-RTU and Modbus-TCP. A complete register with all signals specified can be requested from eSite Power Systems.
The eSite x10 provides support for SNMP communication. A complete MIB with all signals specified can be requested from eSite Power Systems.
The eSite x10 supports communication via the CAN protocol and can be used with e.g. Li-ion batteries or external LEM current sensors.
The eSite x10 software also supports joint operation with one (1) additional connected eSite x10 unit. Connecting an additional eSite x10 unit will increase the maximum rectifier power of the system to 21 kW. One unit will act as the Master unit and the other as the Expansion unit. All decisions and controls are processed in the Master unit. Communication between the Master and Expansion units is handled with the CAN protocol. The rectifiers in the Expansion unit are connected to the same phase and receive the same control signals as their counterpart in the Master unit, i.e. rectifiers 1 & 4, 2 & 5, and 3 & 6 are synchronized. Alarms and Errors are presented on the Master unit web pages and on eSite Tools. The customer loads can be connected to a common bus bar or separately to each unit.
At least one external battery sensor has to be mounted on a system with an Expansion unit connected. Configurations are made at the web pages.
Contact eSite Power Systems for more information of how to install and configure a site with an Expansion unit.
The table shows the pin descriptions and the default configurations for the I/O screw terminals on the RSY and RSC models. The digital inputs can be configured to normally open or normally closed.
Model: RSY (Serial number: 7246XXX)
Model: RSC (Serial number: 7247XXX)
*connected from factory.
Copyright © 2021 eSite Power Systems AB
Make sure that air flows unobstructed through the airways. Remove debris, dry leaves, spider web or any dirt that obstruct normal airflow (see figure 7.1).
Copyright © 2021 eSite Power Systems AB
Warning
Do not reboot eSite x10 before all active alarms are handled.
Check the alarm list for the most severe active alarm and follow the instructions for suggested actions.
Document your actions.
When the issue is resolved, the alarm automatically clears itself and disappears from the alarm list in eSite Web and eSite Tools.
If more alarms are active, start from step one with the next alarm.
If any alarm is still active and cannot be cleared, contact first line support.
The Alarm control monitors eSite x10 and its associated systems and trigger alarms. Alarms are indicated in eSite Web and eSite Tools. Some thresholds for alarms are configured via eSite Web and eSite Tools. Alarms are divided into the following types based on severity.
The LEDs on the Lower Main gives information about the system condition
This section outlines the defined alarms for eSite x10 and how they are activated/reset, along with a description of possible causes and recommended actions.
Description: Any rectifier reports critical error Severity: Fatal
Description: Breaker to battery bank has tripped. Batteries are unable to provide power to eSite x10 and customer load. Only external power sources (genset, grid and solar) can sustain the site. System mode: Enters Safe mode. Genset runs continuously until issue solved. No backup time is available. Severity: Fatal
Description: Battery charge current sensor inside the main compartment has failed. System mode enters Safe mode. Charge request continuous until issue solved. Severity: Fatal
Description: Battery door open on eSite x10 cabinet. Severity: Warning
Description: The temperature sensor is placed inside the battery cabinet. The average battery temperature has been high for along duration and the battery bank takes permanent damage if not fixed. Severity: Error
Description: The temperature sensor is placed inside the battery cabinet. Battery temperature is high and the battery bank takes permanent damage if not fixed. Severity: Warning
Description: The temperature sensor is placed inside the battery cabinet. Battery temperature is very high and the battery bank takes permanent damage if not fixed. Severity: Fatal
Description: Temperature in battery cabinet is significantly larger than outside temp. Severity: Warning
Description: All Voltage sensors has failed. Limp home value of 40V is used. Severity: Fatal
Description: Battery voltage is high and the batteries will take permanent damage if issue is not resolved Severity: Warning
Description: Battery voltage is low and the customer load disconnects if not resolved. eSite x10 is not able to receive sufficient power from the input power sources. Severity: Fatal
Description: The main CPU frequency is throttled due to high temperature, the maximum rectifier output power has been reduced. Severity: Warning
Description: eSite Web does not show the correct values, or no values at all, and can show database related errors. Signal data may not be logged on site. Site configuration can be incorrect with default values used instead. Severity: Error
Description: Total load is higher than the rated value on the expansion unit, see data sheet. Severity: Warning
Description: The Main Compartment is bypassed and HP load receives power directly from the battery bank. The function is used when replacing the Main Compartment. Batteries can take permanent damage as the batteries cannot be disconnected from the load with the LVD contactors. Severity: Fatal
Description: The expansion unit Main Compartment is bypassed and LP load receives power directly from the battery bank. The function is used when replacing the Main Compartment. Batteries can take permanent damage as the batteries cannot be disconnected from the load with the LVD contactors. Severity: Fatal
Description: Battery charge current sensor inside the expansion unit main compartment has failed. System mode enters Safe mode. Charge request continuous until issue solved. Severity: Fatal
Description: Communication to expansion unit I/O controller has failed, eSite x10 is not able to read I/O signals. Severity: Fatal
Description: The sensor used to measure the external solar is faulty Severity: Warning
Description: Genset tank has been filled. Severity: Information
Description: The fuel sensor is detecting a sudden fuel loss. Severity: Warning
Description: Fuel is below the setup low volume threshold Severity: Information
Description: Fuel Sensor measurements are below the very low volume threshold. Severity: Warning
Description: Modbus Communication to genset panel has failed and eSite x10 is unable to read data from the genset. Severity: Warning
Description: Genset external alarm has tripped Severity: Warning
Description: Genset does not start on command. Severity: Fatal
Description: Genset does not stop on command. Severity: Error
Description: A genset is running. Severity: Information
Description: Time limit for genset maintenance has expired. Scheduled Hours to maintenance. Severity: Warning
Description: Input Power from grid is not available. Voltage is out of range 85 – 300 V. Frequency is out of range 45 – 65 Hz. Severity: Warning
Description: The Main Compartment is bypassed and HP load receives power directly from the battery bank. The function is used when replacing the Main Compartment. Batteries can take permanent damage as the batteries cannot be disconnected from the load with the LVD contactors. Severity: Fatal
Description: High priority customer load is disconnected due to low voltage. Severity: Fatal
Description: Total high priority load is higher than the rated value, see data sheet. Severity: Error
Description: Communication to I/O controller has failed, eSite x10 is not able to read I/O signals. Severity: Fatal
Description: Max total power load threshold is reached. Severity: Warning
Description: Max total power load threshold is reached. Severity: Warning
Description: System voltage is below 42 V and the HP load has been disconnected using the LVD contactor. Severity:
Description: System voltage is below 42 V and the HP load has been disconnected using the LVD contactor. Severity:
Description: The Main Compartment is bypassed and LP load receives power directly from the battery bank. The function is used when replacing the Main Compartment. Batteries can take permanent damage as the batteries cannot be disconnected from the load with the LVD contactors. Severity: Fatal
Description: Low priority customer load has been disconnected due to low battery voltage. Severity: Fatal
Description: The expansion HP load current has exceeded 180 A. The expansion HP load is disconnected using the LVD contactor. Severity: Fatal
Description: The expansion LP load current has exceeded 180 A. The expansion LP load is disconnected using the LVD contactor. Severity: Fatal
Description: The HP load current has exceeded 180 A. The HP load is disconnected using the LVD contactor. Severity: Fatal
Description: The LP load current has exceeded 180 A. The LP load is disconnected using the LVD contactor. Severity: Fatal
Description: Communication to rectifier controller has failed. The rectifier may not deliver power. Severity: Error
Description: Due to high internal temperature, the maximum rectifier output power has been reduced. Severity: Warning
Description: Rectifier does not supply power. Severity: Fatal
Description: Solar converter measures the input voltage above the threshold in the data sheet. The array has too high voltage. No solar power is produced. Severity: Fatal
Description: Reversed polarity. Solar panel minus terminal may be connected to ground. Severity: Fatal
Description: Communication to solar converter has failed. eSite x10 is not able to read solar signals. Severity: Fatal
Description: Solar converter does not supply power. Severity: Fatal
Description: Any of the solar converters measures its voltage ±1V compared to system voltage. severity: Error
Description: External Surge protection for genset/grid 100 kA has tripped. Severity: Error
Description: Sensor measuring the internal voltage in Main Compartment has failed. Voltage measurement from the rectifier or solar converters is used instead. Severity: Warning
Description: The sensor measuring the tenant current is invalid. Severity: Warning
Description: The values of the battery voltage sensor and the system voltage sensor measurements are not matching. The voltage difference has exceeded a predefined threshold. Severity: Error
External alarms are communicated from external sources like Genset or Lithium-ion batteries and can be forwarded to the user by eSite x10. To receive this type of alarms, a communication are required to the source.
The following alarms can be configured for Genset 1 and 2, in the local eSite Web configuration page:
HighBatteryVoltage
LowBatteryVoltage
ChargerAcFailure
FailToStart
FailToStop
LowCoolantTemperature
HighCoolantTemperature
LowOilPressure
OverSpeed
LowFuelLevel
HighAcVoltage
LowAcVoltage
UnderFrequency
Overload
Overcurrent
ShortCircuit
ReverseKW
ReverseKVAR
FailToClose
EmergencyStop
OilPressureSwitch
CoolantTemperatureSwitch
FuelLevelSwitch
WarningAlarmActive
ElectricalAlarmActive
ShutdownAlarmActive
ControlUnitFailure
ControlUnitNotConfigured
Alarm1
Alarm2
Alarm3
The alarms communicated from Li-ion batteries differ between the various manufacturers. Each supported battery has its own list of alarms which is configured in the eSite x10 when the specific battery is selected in the local web configuration page.
The eSite x10 can be configured to read data from a battery monitoring system (BMS) used on a lithium-ion battery bank. The data is used to control the charge and discharge of the battery.
All communication to the battery bank is made via the RS485 connector, connected to the C7-1 (Data A) and C7-2 (Data B) ports on the eSite x10 Lower Main I/O screw terminals and the corresponding connectors on the battery. The protocol is Modbus-RTU and all data signals and alarms are pre-defined from a Modbus register provided by the battery manufacturer.
The following steps describe the configuration of one of the supported lithium-ion batteries. Note that the settings differ between different battery manufacturers.
Follow the manufacturer's installation guide to install the batteries and connect them to the eSite x10 48V bus bars.
Connect the battery RS485 (Data A) output wire to the eSite x10 RS485 connector, C7-1 (Data A).
Connect the battery RS485 (Data B) output wire to the eSite x10 RS485 connector, C7-1 (Data B).
It is important to assign a unique Slave-ID to each Li-ion Battery Monitoring Unit (BMU). Note that Slave-ID '1' must be assigned to the BMU with RS485 communication cable connected (the 'main' BMU) and continue in ascending order with the following BMU(s). How to set the Slave-IDs is specified in the manufacturer's manual.
To complete the eSite x10 configuration for Li-ion battery communication, follow these steps:
Connect to the eSite x10 Wi-Fi named 'eSite + serial' number.
Login to the site with the user: Admin. The password is provided by eSite Power Systems.
Open the Configuration page and select the Battery tab.
Select a battery template for the installed Li-ion battery and press the 'Press to select battery template' button.
Open the Configuration page and select the Modbus Communication tab.
Enable the communication to Li-ion BMS by selecting the 'ON' setting.
Set the number of installed Li-ion modules, max number of modules is 16. The eSite x10 requires that the first module (BMU) is assigned slave-ID '1'.
Check the Modbus communication protocol, should match the selected battery type.
Set the RS485 Baudrate according to the manufacturer's manual.
After making any changes, restart the Modbus communication by pressing 'Restart'.
To check the communication, open the Battery page and check the BMU status under the Battery menu tab.
Many manufacturers of Genset AMF panels can communicate via a serial line (daisy-chain). eSite x10 supports communication over Modbus-RTU protocol half-duplex RS-485. Over this communication, it is possible to read data, alarms and set commands. Two (2) Genset panels can be configured at one site.
Figure A.2 shows an example of the local web configuration of a DSE-7320 AMF panel. Baudrate is 9600 and Slave-ID on the AMF panel is set to 16.
The eSite x10 includes 8 different controllers which all can be updated with new firmware if needed. All updates are triggered by a manual execution via the local web page or remotely via eSite Tools, performed by eSite Power Systems.
The main controller is based on the Linux operation system. Before you update the system, always make a backup of the configuration files, see section Backup Data.
Make sure you have a firmware file name flex-update-field.img located on a USB stick or your PC.
Connect to the eSite x10 Wi-Fi named 'eSite + serial' number.
Login to the local eSite x10 web page as Admin. The password is provided by eSite Power Systems.
Press the Configuration menu and then the System tab (see figure A.3).
Press the "Update eSite x10 Controllers" link.
In the update page, press the "Select file" link, find the update file on your PC and then "Upload file". Follow the instructions from the page.
The update can take up to 5 minutes to process.
After the update, log in again and verify that the new version is presented in the About page.
Updates of the micro controllers are performed in the same way as for the Main controller. Before updating the micro controllers, make sure you have received a valid update package from eSite Power Systems.
The package name can be anything but must have an extension of .slv
Follow steps 2-6 above.
Return to system page.
Downloading a backup of configuration data is useful when sharing data between sites. You can share Battery configurations and Modbus setups. It is also possible to backup log data.
Connect to the eSite x10 Wi-Fi named 'eSite + serial' number.
Login to the local eSite x10 web page as Admin. The password is provided by eSite Power Systems.
Press the Configuration menu and then the System tab.
Press the "Backup Data" link (see figure A.4).
In the backup page, select the desired data in the drop-down menu, write a file name (must end with .flx) and press the download button.
It is possible to upload a downloaded configuration or upload a configuration delivered from eSite Power Systems.
Connect to the eSite x10 Wi-Fi named 'eSite + serial' number.
Login to the local eSite x10 web page as Admin. The password is provided by eSite Power Systems.
Press the Configuration menu and then the System tab.
Press the "Upload Configuration Data" link.
In the restore page, select a file by pressing the link, the file must end with .flx, then press "Upload file".
Follow the instructions from the page.
Return to system page.
eSite x10 requires a license file to be installed to get all desired options enabled. Without any license file installed, the system will operate in with a very limited functionality. Before site commissioning, make sure you have received a valid license file which matches the serial number of the eSite x10 and that includes the options you have purchased.
A license file can match several serial numbers with different options. Make sure you have the correct one before starting the site commissioning.
If firmware updates are necessary as part of the site commissioning, please install the updates before installing the license file.
All eSite x10 systems are delivered without a license file installed. When the eSite x10 is powered up for the first time, it will operate in 'Delivery mode' where the following default options are set:
Input Source A is set to Grid
Input Source B is disabled
Built-in Solar converters are disabled
Tenant monitoring is disabled
Login to the local eSite x10 web page as Admin and press 'next' on the Welcome screen to start the site commissioning guide (see figure A.5).
If any controller firmware needs to be updated, press the 'Update Controller Software here!' link and install the updates.
Press the 'Install license file here!' link to enter the license update page.
On the license update page (see figure A.6), press the "Select file" link and choose the license file from your PC and then press "Upload file". Press return to System pages when finished.
A log file is presented the result of the update. After the update, press 'Return to the system pages'.
If you need to update the License file due to changes in the options, please go to the configuration pages under the System tab on the eSite Web.
Press the "Update eSite x10 License" link and follow the procedure above.
The battery temperature sensor consists of a thermistor on a cable, standard length 5 m. Place the sensor in the battery cabinet in the centre of the battery bank.
The battery voltage sensor probes connect directly to the battery terminals. They are polarity sensitive, but are protected for reversed polarity. On the negative probe there is a tubular fuse (slow acting, 1 A, 48 V). The probe is connected to the blue internal cables in the Connection Compartment.
For external current measurements, eSite x10 uses complementary LEM current sensors (see figure 9.1). LEM current sensors utilize the CAN protocol for communication with the eSite x10. The CAN cable kit provided by eSite Power Systems is specifically prepared for use with LEM sensors. The white contacts can be used to connect several current sensors. The connection order does not matter.
The current sensors may be used for battery banks, external solar converters and tenants.
The following CAN IDs are presently configurable:
001 (3C1)
002 (3C2)
003 (3C3)
004 (3C4)
005 (3C5)
006 (3C6)
007 (3C7)
008 (3C8)
009 (3C9)
000 (3C0)
Fuel sensor 1
Fuel sensor 2
The genset start battery charger is a DC to DC converter with a fuse of 7.5 A, 48 V. It is powered from LP. Output voltage shall be 13.5 V.
All 24 V, GND and 12 V connection points on the I/O terminals, according to I/O list, can be used, but its preferred to use the terminal when available.
Replace the Main Compartment only if suggested by an alarm or by a suggested action in the troubleshooting chapter. All prior corrective actions must be tried and failed.
Fill in a replacement report for each unit before it is replaced. Send the report to eSite Power Systems. A Return Material Authorization (RMA) number is provided from eSite Power Systems. The RMA number must be clearly labelled on the returning box to eSite Power Systems for the warranty to be processed.
A Main Compartment guides B Lower Main C Mounting frame
For replacement of eSite x10 Main Compartment and for troubleshooting during the replacement use the tools listed below.
A Torx T10 and T20 B Ring spanner 8 mm and 17 mm C Screwdriver 2.4 mm and 5 mm (common blade) D Screwdriver PZ2 (Pozidriv) E Gloves F Wire cutter G Network cable H Laptop I Goggles J Pen K Camera / smartphone L Socket wrench 13 mm and 16 mm M Multimeter N Ampere clamp
Warning
The Main Compartment must not be lifted by one person alone.
Before you lift the Main Compartment you must:
know the weight of the Main Compartment (70 kg).
make sure the area is clear of obstruction.
make sure there are no wet or slippery surfaces in the area.
When you lift the Main Compartment, do as follows:
Stand as close to the box as possible.
Make sure you are steady on your feet and keep a good balance.
Keep your back straight and use your legs and hips to lower yourself down to the box.
Get a firm hold of the Main Compartment with your hands.
Lift slowly by extending your legs with your back straight.
Warning
Do not touch the pins on the upper part of the Connection Compartment. Once the Main Compartment is removed, there is live power in the pins. There is a risk for electrical shock.
Warning
During operation, the Main Compartment may become very hot. Ensure that it has cooled down sufficiently before undocking it. There is a burn hazard.
Caution
When out of the box the lower part of the Main Compartment must not touch soil or grass.
Caution
The two Main Compartment guides must slide into the slots for the Main Compartment to be correctly installed.
Make sure that the Main Compartment is tight together with the Connection Compartment to prevent problems because of distance between the compartments. The dark grey area on the Main Compartment must completely cover the dark grey area of the Connection Compartment.
A I/O screw terminals B LED 1–3 C Ethernet socket D Antenna socket 1 – GSM antenna E Antenna socket 2 – Wi-Fi antenna (RSY model) F 1 x USB port (2 x USB for RSY model) used for software updates (not to be used for mobile phone charging) G SIM card holder
Caution
Be careful when installing the SIM card. The holder is easily damaged.
The sensors and antennas are connected to the Lower Main. When the Main Compartment is docked, the Lower Main is accessed through the Connection Compartment.
The I/O screw terminals are categorized as TNV-2 circuit according to IEC 60950-1.
See section for more information and how to set parameters.
On the side of the Connection Compartment there are two visual indicators, one green LED and one red LED. The LEDs give an on-site indication of the state of the system. This functionality is optional. See 9.6 for connection details.
Description: The ambient (outside) temperature sensor is not properly connected. See 9.1 for connection details. Severity: Error
Description: Faulty Battery Current sensor placed inside the connection compartment (Optional for dual battery strings). See 9.4 for connection details. Severity: Error
Description: The sensor is not properly connected. The polarity is wrong. See 9.2 for connection details. Severity: Fatal
Description: The sensor measuring the battery voltage is faulty. System voltage will be used as a fall back. Connection problem. See 9.3 for connection details. Severity: Error
Description: Connection Compartment Lid is open. See 9.8 for connection details. Severity: Warning
Description: Sensor measurements are outside its specified voltage range. See 9.5 for connection details. Severity: Warning
To receive Genset alarms, a Modbus communication is required to the AMF panel, see how to install it.
See how to install and configure a Li-ion battery.
Copyright © 2021
All settings are made from the local eSite Web pages under An overview of the configuration pages is shown in figure A.1.
All communication to the AMF panel is made via the RS485 connector, connected to the C7-1 (Data A) and C7-2 (Data B) ports on the eSite x10 and the corresponding connectors on the panel. All settings such as baudrate and slave-ID are made in the local eSite Web pages.
To configure the Modbus data and alarms requires knowledge of how the AMF panel Modbus register is set up. You may find a detailed description of the parameters
It is possible to import pre-defined AMF-panel configurations by following the steps in the section. Contact eSite Power Systems for support.
Copyright © 2021
In case of an issue with eSite x10 an alarm is triggered. For more information on how to handle alarms, see section . This chapter is a complement to the Alarm list and it is used for issues that do not have an alarm connected to them.
Copyright © 2021
The ambient air temperature sensor consists of a thermistor on a cable. Place the sensor hanging below the Connection Compartment. For more information about 12 V, 24 V and GND see section .
For more information about 12 V, 24 V and GND see section .
The fuel sensor must be supplied with 24 V and 0‒10 V output. The colour coding below is valid for fuel sensors supplied by eSite Power Systems. For more information about 12 V, 24 V and GND see section .
For more information about 12 V, 24 V and GND see section .
Default configuration: 24 V = no alarm, 0 V = alarm. For more information about 12 V, 24 V and GND see section .
Copyright © 2021
Fatal
eSite x10 disconnects or has already disconnected customer load due to a severe problem. The equipment can be permanently damaged.
Error
eSite x10 runs at degraded performance but can provide full power to the customer load.
Warning
eSite x10 runs at full functionality but an abnormal event has occurred.
Information
eSite x10 runs at full functionality and a normal event has occurred.
On
Off
eSite x10 is functional but there can be active alarms. This state is active when none of the two below states are active.
Log in to eSite Web to see if any alarm is active. Solve any active alarms.
Off
Flashing
A serious error has occurred. Genset 1 start alarm and Genset 2 start alarm can trigger this state.
Log in to eSite Web to see what alarm that is active. Solve the active alarms.
Off
On
The customer load is disconnected. LP LVD disconnected and HP LVD disconnected can trigger this state.
Log in to eSite Web to see what alarm that is active. Solve the active alarms.
Off
Off
eSite x10 is off. The LEDs may be broken or do not get power.
For more information see 9.6 Connection compartment LEDs
LED 1
LED 1 Red is flashing if the control system is not running.
LED 2
LED 2 Green ON indicates that the Main controller has booted and is running.
LED 3
Not in use.
Temperature sensor or sensor cable is faulty.
Check the ambient air temperature sensor for damages, replace if necessary.
The alarm is triggered on the I/O through the analogue signal cable that connects the temperature cable to the I/O terminal. Outside 3.16 V =–39.94 °C and 0.60 V = 68.24 °C the alarm is triggered.
eSite x10 I/O voltage received is 0 V or 10 V depending on temperature configuration.
A rectifier has a critical alarm.
Replace eSite x10 Main Compartment.
Hardware faulty
Main Compartment replaced and communication restored
- CAN Communication signal cable faulty. - Sensor Hardware failure. - Current sensor option “enabled“ but no sensor installed.
1) Make sure that there are no interruptions on the signal cable. 2) Replace the faulty sensor. 3) Ensure that a sensor is installed.
Sensor Hardware/ Communication failure
Communication with sensor is established, correct current measurement values data.
- Battery failures. - MCB faulty. - Communication signal cable faulty. - I/O incorrect configuration.
1) Verify the connection on the I/O terminals. 2) Ensure that the battery fuses are dimensioned for the battery short-circuit and not for the over current. 3) Check / measure the condition of each battery. 4) Ensure that the I/O configuration matches the MCB settings (Normally open / Normally closed). 5) Check the battery breaker for burning marks, short circuit etc. Replace if necessary. 6) Check the battery bank power cable connection. 7) Make sure that there are no interruptions on the signal cable.
The alarm is triggered on the I/O through the Digital signal cable that connects the MCB to the I/O terminal.
eSite x10 I/O voltage received is 24 V or 0 V depending on I/O configuration (Normally open / Normally closed).
Sensor Hardware failure
Replace eSite x10 Main Compartment
Sensor Hardware failure
Main Compartment replaced and communication restored.
Cabinet door open. Communication signal cable faulty. I/O incorrect configuration.
1) Check the battery cabinet door on site and close it if it is unintentionally open. 2) Check the battery cabinet door switches for damages. Replace if necessary. 3) Make sure that there are no interruptions on the signal cable. 4) Verify the connection on the I/O terminals. 5) Ensure that the I/O configuration matches the MCB settings (Normally open / Normally closed).
The alarm is triggered on the I/O through the Digital signal cable that connects the battery cabinet door switch to the I/O terminal.
eSite x10 I/O voltage received is 24 V or 0 V depending on I/O configuration (Normally open /Normally closed).
1) Insufficient cooling of battery cabinet. 2) Fans or AC cooling failure. 3) Filter clogged. 4) Damaged batteries. 5) Damaged battery cabinet 6) Door is open or not closed properly. 7) Insufficient shading of battery cabinet
1) Inspect fans and AC cooling for failure. 2) Inspect filter and replace if dirty. 3) Inspect the batteries for visible injuries/bulges. 4) Inspect cabinet, doors and high power cables for damages. 5) Inspect condition/existence of roof over battery cabinet/ Improve shading over battery cabinet
The alarm is triggered at 37.0°C, the average temperature measured over 1 week.
The alarm trigger temperature conditions are: [x °C – 0.2 °C].
1) Insufficient cooling of battery cabinet. 2) Fans or AC cooling failure. 3) Filter clogged. 4) Damaged batteries. 5) Damaged battery cabinet 6) Door is open or not closed properly. 7) Insufficient shading of battery cabinet
1) Inspect fans and AC cooling for failure. 2) Inspect filter and replace if dirty. 3) Inspect the batteries for visible injuries/bulges. 4) Inspect cabinet, doors and high power cables for damages. 5) Inspect condition/existence of roof over battery cabinet/ Improve shading over battery cabinet
The alarm is triggered at 42.0°C real-time/ instantaneous measured value.
The alarm trigger temperature conditions are:[x °C – 2.0 °C].
1) Insufficient cooling of battery cabinet. 2) Fans or AC cooling failure. 3) Filter clogged. 4) Damaged batteries. 5) Damaged battery cabinet 6) Door is open or not closed properly. 7) Insufficient shading of battery cabinet
1) Inspect fans and AC cooling for failure. 2) Inspect filter and replace if dirty. 3) Inspect the batteries for visible injuries/bulges. 4) Inspect cabinet, doors and high power cables for damages. 5) Inspect condition/existence of roof over battery cabinet/ Improve shading over battery cabinet
45 °C (SS) sensor valid
The alarm trigger temperature conditions are:[x – 2.0 °C].
1) Cooling equipment might have stopped working. 2) Insufficient shading of battery cabinet.
1) Inspect cooling equipment and ensure correct functionality. 2) Check if there is a way to increase shading.
12 °C (SS), sensors valid
x - 2 °C
1) Sensor or sensor cable is faulty 2) The battery cabinet temperature is severely high.
1) Make sure that the sensor and sensor cables are not damaged. 2) Check the battery cabinet for possible causes to high temperature.
The alarm is triggered on the I/O through the analogue signal cable that connects the temperature cable to the I/O terminal.
eSite x10 I/O voltage received is 0 V or 10 V depending on temperature configuration.
System hardware failure
Replace eSite x10 Main Compartment
All Voltage sensors has failed
Main Compartment replaced and voltage measurement restored
There is another power source connected to the system, which is not controlled by eSite x10.
Check on the site if there is any other power source connected. Disconnect the power source.
Default 60 V. This threshold is temperature compensated according to the battery calibration.
The alarm trigger temperature condition is: x –0.5 V.
- Genset failed to start. - Genset failed to produce sufficient power to customer load and battery bank. - Grid not available.
1) See alarm "Genset start: Alarm". 2) Verify genset rating configuration 3) Verify grid max current configuration
Default = 46.5 V(configurable).
Default = 48.5 V(configurable).
- Battery voltage sensor faulty connected. - Reverse polarity. - eSite x10 Main Compartment is not properly docked to the Connection Compartment.
1) Check the sensor installation. 2) Verify the polarity of the sensor cables. 3) Check the Main Compartment connection. 4) Check the fuse on the negative side of the battery voltage sensor cable.
Sensor voltage >70V or <10V
N/A
- Connection Compartment Lid is open. - Communication signal cable faulty.
1) Check the Connection Compartment Lid on site. Close the Connection Compartment Lid if it is unintentionally open. 2) Check the Connection Compartment Lid switches for damages. Replace if necessary. 3) Check if the signal cable is faulty by checking if there are interruptions on it. 4) Ensure that the I/O configuration matches the MCB settings (Normally open / Normally closed).
The alarm is triggered on the I/O, through the Digital signal cable that connects the Connection Compartment Lid switch to I/O terminal.
The I/O voltage received is 24 V or 0 V depending on the I/O configuration (Normally open / Normally closed).
- High outside temperature (>Nominal Temperature). - Direct sunlight placement. - Close to a heat source. - Dirty heat sink. - Hardware malfunction.
1) Improve the shading over the eSite x10 unit if required. 2) Make sure that eSite x10 is not placed close to a heat source. 3) Clean the heat sink according to section "Maintenance eSite x10" 4) Contact first line support.
Too high internal temperature.
Normal internal temperature.
- Error in databases. - Trying to access eSite Web too soon after a reboot.
1) Reboot main controller to restore database. 2) Press the "Factory reset" button, see 4.9.15 Shutdown/Restart
Database Open/read/write error
No errors at init.
Customer is drawing more power than configured on expansion unit.
1) Measure the total power of the load connected to eSite x10 on site. 2) Reduce the total system power drawn. 3) Balance load more evenly between master and expansion unit
Default load = 10 kW for 10 sec (configurable).
The alarm trigger temperature conditions are: x– 100 W.
– Expansion unit's Main Compartment is being replaced. - Misuse of the bypass functionality.
Check why the bypass breaker is tripped, disengage the bypass breaker when the issue is solved.
The alarm is triggered on the I/O through the Digital signal cable that connects the bypass breaker indication to the I/O terminal.
eSite x10 I/O voltage received is 24 V.
– Expansion unit Main Compartment is being replaced. - Misuse of the bypass functionality.
Check why the bypass breaker is tripped, disengage the bypass breaker when the issue is solved.
The alarm is triggered on the I/O through the Digital signal cable that connects the bypass breaker indication to the I/O terminal.
eSite x10 I/O voltage
Sensor Hardware failure
Replace eSite x10 Main Compartment
Sensor Hardware failure
Main Compartment replaced and communication restored.
I/O hardware fail.
Replace eSite x10 expansion unit Main Compartment.
No communication response from I/O.
Main Compartment replaced and communication restored.
Current sensor is damaged. Sensor is not connected.
Check connections for current sensor. Replace sensor
N/A
N/A
Fuel tank has been refilled
N/A
4 % fuel increase is detected between a rolling period of 1800 sec.
The alarm will reset it self within one hour after the filling was detected.
Fuel theft or leakages.
Check the fuel tank and the fuel sensor on site.
4 % fuel decrease is detected between a rolling period of 1800 sec.
Resets itself after a refill.
Not enough fuel in the tank.
Refill diesel
Default value: below 300 litres(configurable).
Default value: 300 + 20 litres(configurable).
- The Fuel Sensor is disconnected. - The Fuel Sensor is not installed correct. - The Fuel Sensor is faulty.
1) Check sensor installation. 2) Check the sensor polarity. 3) Verify the sensor configuration. 4) Check if the sensor is faulty.
The alarm is triggered on the I/O, through the analogue signal cable that connects the fuel sensor to the I/O terminal.
eSite x10 I/O voltage received is 0 V or 10 V depending on fuel sensor configuration.
Not enough fuel in the tank.
Refill fuel
Default value: below 200 litres(configurable).
Default value: 200 + 20 litres(configurable).
- Communication cables between eSite x10 and genset are damaged. - Genset start battery is empty. - Incorrect Genset Modbus settings.
1) Check the communication cables from eSite x10 to genset for damage. 2) Check the genset and repair if required. 3) Ensure that eSite x10 genset Modbus configuration matches the genset control panel settings.
No communication response from genset.
Restored communication.
Alarm depending on Genset type and IO.
1) Check the genset to make sure it is not damaged. 2) Make sure that there are no interruptions on the signal cable. 3) Ensure that the I/O configuration matches the MCB settings (Normally open / Normally closed).
No communication response from genset.
Restored communication.
- Genset battery empty or faulty. - No fuel. - Genset alarm. - Communication to genset controller broken. - Power cable between eSite x10 and genset are faulty. - The genset is manually forced to start by someone on site.
1) Check the genset battery and generator system. Charge battery if necessary. 2) Fill up fuel. 3) Check and reset error in genset.
No voltage from genset is detected by eSite x10 for 5 min.
The alarm resets when the input genset voltage is detected.
Genset is manually forced to run by pressing the start button on the genset panel.
1) Make sure that the genset is in auto mode / remote control mode. 2) Verify the start signal from eSite x10 to genset.
Genset is commanded off but eSite x10 is still detecting voltage for 5 min.
Genset is commanded off and no voltage has been received for 1 min.
eSite x10 started a genset.
N/A
Any genset is running
N/A
Maintenance has not been performed.
Perform genset maintenance according to genset documentation.
Default 0 hours left to maintenance.
The timer for genset maintenance is reset.
– Grid power temporarily out. - Grid breaker tripped.
1) Check if the grid provides power. 2) Check grid breaker. Repair if necessary.
AC Voltage and frequency input is out of range for 10 sec.
AC Voltage and frequency input is in range.
– Main Compartment is being replaced. - Misuse of the bypass functionality.
Check why the bypass breaker is tripped, disengage the bypass breaker when the issue is solved.
The alarm is triggered on the I/O through the digital signal cable that connects the bypass breaker indication to the I/O terminal.
eSite x10 I/O voltage received is 24 V.
– System voltage has dropped below threshold. - No incoming power to eSite x10 is available.
Make sure that the power sources are working.
Default 43.5 V.
Default 48 V.
– The customer load is not installed correct. - Incorrect use of High priority load and Low priority load.
1) Verify customers connection at site. 2) Consult the Installation manual for correct use of High priority power and Low priority power.
1.5 kW for 10 sec
x – 100 W
I/O hardware fail.
Replace eSite x10 Main Compartment.
No communication response from I/O.
Main Compartment replaced and communication restored.
Tenant is drawing more power than configured.
1) Check/measure the total power load connected to eSite x10 on site. 2) Reduce the total power drawn from the system.
Default load = 5kW for 10 sec(configurable).
Alarm trigger temperature conditions are: x– 100 W.
Customer is drawing more power than configured.
1) Check/measure the total power load connected to eSite x10 on site. 2) Reduce the total system power drawn.
Default load = 10 kW for 10 sec (configurable).
The alarm trigger temperature conditions are: x– 100 W.
No incoming power to eSite x10 expansion unit is available.
Make sure that the power sources are working. Alarms triggered before could be: 'Genset failed to start' or 'Grid not available'.
System voltage has dropped below threshold.
Alarm manually cleared.
No incoming power to eSite x10 is available.
Make sure that the power sources are working. Alarms triggered before could be genset failed to start or grid not available.
System voltage has dropped below threshold.
Alarm manually cleared.
– Main Compartment is being replaced. - Misuse of the bypass functionality.
Check why the bypass breaker is tripped, disengage the bypass breaker when the issue is solved.
The alarm is triggered on the I/O through the Digital signal cable that connects the bypass breaker indication to the I/O terminal.
eSite x10 I/O voltage received is 24 V.
– System voltage has dropped below threshold. - No incoming power to eSite x10 is available.
Make sure that the power sources are working.
45 V + 300 sec
The load is reconnected when battery voltage is above 48 V and produced current from the rectifiers is 30 A within 30 sec or battery voltage is above 52 V.
– Customer draws a higher power than allowed - Short circuit on site.
1) Check/measure on site the total power load connected to the eSite x10. Reduce load if too high. 2) Check the customer equipment and connection.
Current exceeds threshold.
Alarm is manually cleared.
– Customer draws a higher power than allowed - Short circuit on site.
1) Check/measure on site the total power load connected to the eSite x10. Reduce load if too high. 2) Check the customer equipment and connection.
Current exceeds threshold.
Alarm is manually cleared.
– Customer draws a higher power than allowed - Short circuit on site.
1) Check/measure on site the total power load connected to the eSite x10. Reduce load if too high. 2) Check the customer equipment and connection.
Current exceeds threshold.
Alarm is manually cleared.
– Customer draws a higher power than allowed - Short circuit on site.
1) Check/measure on site the total power load connected to the eSite x10. Reduce load if too high. 2) Check the customer equipment and connection.
Current exceeds threshold.
Alarm is manually cleared.
Rectifier hardware fail.
Replace eSite x10 Main Compartment.
No communication response from rectifier.
Main Compartment replaced and communication restored.
– High outside temperature (>Nominal Temperature). - Direct sunlight placement. - Close to a heat source. - Dirty heat sink. - Hardware malfunction.
1) Improve the shading over eSite x10 if required. 2) Make sure that eSite x10 is not placed close to a heat source. 3) Clean the heat sink according to section "Maintenance eSite x10" 4) Contact first line support.
To high rectifier internal temperature.
Normal rectifier internal temperature.
Rectifier hardware fail.
Replace eSite x10 Main Compartment.
Hardware faulty
Main Compartment replaced and communication restored.
Incorrect solar panel installation.
Measure the array voltage and ensure that not too many panels are connected in series, thereby exceeding the array voltage range.
Voltage exceeding the threshold.
Automatically cleared when trigger condition is solved. System check every 10 min.
Faulty connected solar array.
1) Measure voltage to see the polarity of the array. 2) Check the connection cables.
Reversed polarity detected.
Automatically cleared when trigger condition is solved. System check every 10 min.
Solar converter hardware fail.
Replace eSite x10 Main Compartment.
No communication response from solar converter.
Main Compartment replaced and communication restored.
Solar converter hardware fail.
Replace eSite x10 Main Compartment.
Hardware faulty.
Main Compartment replaced and communication restored.
Solar hardware fail
If the solar voltage is higher than system voltage, the system will still be safe and run at degraded performance. If the solar voltage is lower than system voltage the batteries might become overcharged witch can be unsafe and shorten the lifetime of the batteries. Ask a Flex admin to check this in diagnostics tab.
Any of the solar converters measures its voltage ±1V compared to system voltage
Voltage diff <± 1V
Over voltage from genset or grid has tripped the surge protection (SPD).
1) Check if surge protection has tripped, replace if necessary. 2) Check signal cables between I/O and the surge protection (SPD).
The alarm is triggered on the I/O through the Digital signal cable that connects the surge protection indication to the I/O terminal.
eSite x10 I/O voltage received is 24 V.
Sensor hardware failure.
Contact first line support.
Sensor hardware failure.
Alarm is manually cleared.
– CAN communication signal cable faulty. - Sensor hardware failure. - Current sensor option enabled but no sensor installed.
1) Make sure that there are no interruptions on the signal cable. Replace if necessary. 2) Verify that there is a sensor installed. 3) Check the ID of the current sensor. 4) Make sure the sensor is not damaged. Replace if necessary. 5) Check the configuration to match installed sensors.
Sensor hardware /Communication failure.
Communication with sensor is established, correct current measurement values data.
– Fuse on the negative battery probe has tripped. - Battery voltage sensor inside the battery cabinet faulty connected on the batteries. - Battery cables faulty connected either onto the Connection Compartment or onto the battery cabinet. - Battery breaker is tripped.
1) Make sure that the battery breaker is engaged. 2) Check the fuse for damages. Replace if necessary. 3) Check the voltage sensor and battery cables for damages. Measure the voltage on the connection compartment side and the battery bank with a multimeter. Compare the voltage values to make sure they have the same value. 4) Check the battery cables, nuts and bolts for burn marks. Replace if necessary.
Voltage diff >2 V. Depending on the temperature and the current in the battery cables.
Voltage diff <1 V
eSite x10 does not start. Lower Main LED is off. No battery bank connected.
By default grid is enabled on source A. To detect voltage source A requires voltage on either phase 1 or phase 3 and source B requires voltage on phase 2. For more information see I/O
Apply power to the AC source input. It can take up to 5 minutes before eSite x10 boots up. When no batteries are connected, check that the battery fuse alarm is triggered and that the system is in Safe mode. Then, if genset is configured the eSite x10 will not try to turn off the genset or switch power source.
eSite x10 does not start. Lower Main LED is off. Battery bank connected.
The Main Compartment is not properly docked. The battery voltage is low. The battery bank is not connected according to instructions.
1. Ensure that the Main Compartment is tightly connected to the Connection Compartment. The dark grey area on the Main Compartment must completely cover the dark grey area of the Connection Compartment. 2. Ensure that the battery voltage is at least 42 V. If the battery voltage is below 42V, check instructions for the previous start-up issue. 3. Ensure that the polarity is correct.
Wi-Fi not detected.
The Wi-Fi name is the same as the Main Compartment serial number. Only Wi-Fi modules supplied by eSite Power Systems are allowed.
1. Ensure that Wi-Fi is enabled on the smart phone/laptop. 2. Use another smart phone/laptop. If Wi-Fi connection continues to fail, use LAN cable to connect.
No connection established with LAN cable.
Connection can be done to eSite Web either through Wi-Fi or via LAN cable.
1. Ensure that the IP of your laptop is set a static IP address 192.168.20.20. 2. Ensure that the laptop network card is enabled. 3. Check that the LEDs next to the Ethernet port flashes. If not, try with another cable or laptop. 4. Ensure that the Lower Main LED is active, check start-up issues.
Solar array voltage but no output current is reported on eSite Web.
If any solar related alarms are active the solar converter powers down and it takes up to 10 min before it is restarted and tries to clear the alarm. After reconnecting the solar array it can take up to 10 min before the array is detected and starts to produce power.
1. Check for any alarm on eSite Web and look up them up in the alarm list. 2. Ensure that the solar panels and arrays are electrically floating and not connected to ground. The solar stand must be grounded separately. 3. Ensure that the polarity is correct and not mixed up with neighbouring solar converters.
No Solar array voltage and no output current is reported on eSite Web.
1. Ensure that the polarity is correct. 2. Check if there is array voltage on the input to the converters. Use a multimeter.
Output power from converter is lower than expected.
Cloudy weather, shade or dirty panels may cause poor performance.
1. Clean panels if necessary and/or remove objects that shade the panels. 2. Check solar array for damages. Even small damages might have a large impact on performance.
Fuel sensor error.
Usually, large fluctuations indicate a broken sensor, bad connection or bad grounding. Some inaccuracy is expected due to uncertainties with tank dimensions, fuel density, fuel sensor etc.
1. Ensure that the Fuel Sensor installation is done as instructed in the Fuel Sensor Installation manual. 2. Clean the air hose. 3. Clean the sensor. 4. Check for damages on the cable. Repair or replace if the cable is bent, squeezed or damaged in any other way. 5. Ensure that the ground resistance is low.
No synchronization with eSite Tools.
GSM or 3G coverage is required on site. eSite x10 continues to operate without synchronization and buffers data until connection is established. Only GSM modules supplied by eSite Power Systems are allowed.
1. Check signal strength and possible error codes under the About menu in eSite Web. 2. Restart modem under the Shutdown / Restart menu in eSite Web. 3. Verify configuration under eSite Tools menu in eSite Web. 4. Ensure that there is sufficient credit on the SIM card. 5. Try the SIM card in a smart phone to ensure that the PIN-code is disabled.
No Connection Compartment LEDs.
eSite x10 is off. The LEDs may be broken or do not receive power.
For more information see Connection compartment LEDs
eSite x10 is not docked correctly.
eSite x10 is docked correctly when the latch is locked and the dark grey area of the Main Compartment covers the dark grey area of the Connection Compartment.
1. Ensure that the pin cover is removed. The Connection Compartment is delivered with a cover for the pin, the cover must be removed before docking the Main Compartment. 2. Ensure that the latch is unlocked and allows for the Main Compartment to dock properly. 3. Ensure that the two springs on the bottom of the Main Compartment are not bent. 4. Ensure that the mounting frame is correctly installed.
Ambient air temp sensor cable 1
Not polarity dependent
12 V
N/A
Ambient air temp sensor cable 2
Not polarity dependent
C8:2 Analogue in 1+
N/A
Resistor 10 k
C8:2 Analogue in 1+
C8:3 Analogue in 1-
Jumper cable
GND
C8:3 Analogue in 1-
Battery temp sensor cable 1
Not polarity dependent
C7:9
Battery temp sensor cable 2
Not polarity dependent
C7:10
CAN cable
Orange – White
C7:5 CAN–H
CAN cable
Orange
C7:6 CAN–L
CAN cable
Brown
GND
CAN cable
Brown – White
12 V
Fuel Sensor cable
Red, 24 V
+24 V
Fuel Sensor cable
Green, GND
GND
Fuel Sensor cable
Yellow, signal
C8:5
Jumper cable
C8:4
GND 24 V
Fuel Sensor cable
Red, 24 V
+24 V
Fuel Sensor cable
Green, GND
GND
Fuel Sensor cable
Yellow, signal
C8:6
Jumper cable
C8:7
GND 24 V
Jumper cable
–
12 V
C2:6
Green LED
–
C2:7
X1 on LED
Green LED
–
GND
X2 on LED
Jumper cable
12 V
C2:6
C2:8
Red LED
–
C2:9
X1 on LED
Red LED
–
C6:10
GND
DCDC 48/12
Input 1 on DC to DC converter
Main earth bar
DCDC 48/12
Fuse (7.5 A) on line
Input 2 on DC to DC converter
Low prio busbar
DCDC 48/12
Input 3 on DC to DC converter
Main earth bar
Door switch
24 V
Door switch
Door switch
C2:5 Connection Compartment lid
Door switch
Serial number equal to and below 065
Use any available GND 24 on the I/O terminals.
Only the 12 V on the I/O terminals are available.
Hanging lever terminals.
X3A, X3B
X4
Only the 12 V on the I/O terminals are available.
1) Switch off the genset breaker. 2) Disengage the grid breakers. 3) Disengage the solar breakers in the Solar junction box. 4) Engage the LP and HP bypass breakers if battery voltage is above 45 V. If not leave them disengaged to avoid damages to the battery bank.
5) Disconnect the I/O terminals.
6) Remove the GSM antenna. 7) Remove the Wi-Fi antenna.
8) Remove the three screws and remove the black plastic lid from the Lower Main. Use a torx T10. 9) Remove the metal plate that covers the modem and the SIM card holder.
10) Slide the SIM card holder to the right and lift the left side. 11) Remove the SIM card from the holder. 12) Close the SIM card holder and slide it back into position. 13) Put the metal plate that covers the modem and the SIM card holder back in place. 14) Put the plastic lid back and tighten the screws.
15) Pull out the latch and lift the Main Compartment. Let it slide up and out of the slots. 16) Fold down the Top Cover for the Connection Compartment as protection for the Connection Compartment. Additional protection from rain and dirt is recommended. 17) Keep the Main Compartment on a clean and dry place while the new Main Compartment is installed. 18) Dock the new Main Compartment. For more information on how to perform the operation see "Dock the Main Compartment"
19) Put the used Main Compartment in the transportation box in which the new Main Compartment is delivered. One styrofoam is for the top of the Main Compartment and one styrofoam is for the bottom. Ensure they are fitted correctly when lowering the used Main Compartment into the package. Pack the Main Compartment properly to prevent any further damages. 20) Mark the box with the serial number and the Return Material Authorization (RMA) number. 21) Close the box lid.
1) Pry the locks open on the transportation box for the Main Compartment. 2) Unpack the Main Compartment and remove the styrofoam. Save the styrofoam for packing the used Main Compartment. 3) Lift the Main Compartment and make sure that the guides on the right and the left side of the unit goes into the slots. 4) Let the Main Compartment slide down the slots to sit on the latch. 5) Pull out the latch and lower the Main Compartment into the correct position and let the latch lock.
1) Remove the three screws and remove the black plastic lid from the Lower Main. Use a torx T10. 2) Remove the metal plate that covers the modem and the SIM card holder.
3) Slide the SIM card holder to the right and lift the left side. 4) Put the SIM card into the holder. 5) Close the SIM card holder and slide it back into position. 6) Put the metal plate that covers the modem and the SIM card holder back. 7) Put the black plastic lid back and tighten the screws.
1) Install the 8 I/O screw terminals on to the Lower Main. Install them according to the labels, C1, C2, C3, C4, C5, C6, C7 and C8.
2) Connect the GSM antenna to the Ant 1 socket on the Lower Main. 3) Install the Wi-Fi antenna in the Ant 2 socket on the Lower Main. 4) Disengage the bypass breakers. 5) Log in and do the site commissioning.
eSite Web is accessed on site via a laptop or a smartphone using Wi-Fi or LAN cable. It provides the user with an overview of the status of eSite x10 and active alarms. It also offers a possibility to configure eSite x10 (see figure 4.1).
eSite Web allows two user levels. Each user requires a user name and a password.
The default passwords is provided by eSite Power Systems.
The passwords can be changed by the Admin user.
Operator
View data and alarms (read only).
Admin
View data and alarms. Configure the system. Update the system and download data.
For configurations, see section Configurations.
For alarm functionality, see section Alarms.
From the first page pages with more detailed information is reached. Click the icons on the menu bar to reach the detailed information and to configure the system.
The eSite Web header (see figure 4.2) contains the following basic information about the specific eSite x10 system.
Site name
Text input from configuration.
Usually town or area where eSite x10 is located.
Site ID
Text input from configuration.
Connects eSite x10 to eSite Tools.
System mode
Auto / Auto Full Charge / Safe Mode / Manual
Describes in what mode eSite x10 is currently operating.
Local date and time
Year - Month - Day Hour : min : sec
Present local date and time.
eSite Tools server connection
Not configured / No connection to server / Synchronized
Indicates the status of the connection to eSite Tools server.
Battery status
Volt and state of charge.
For more information see section "Battery information".
Estimated time to next genset start
Hours / Minutes
Shows the time left until genset starts and at what state of charge this occurs. This information is only visible when charge strategies Static SOC or Partial SOC are active.
The Battery menu provides the information in the table below. For further information about the batteries, read the reference Batteries.
Battery type
Type name selected from configuration.
The battery type is shown in the table header.
State of Charge (SOC)
%
Shows battery state of charge. 0 % = empty batteries with no energy left. 100 % = fully charged.
Battery state
Discharge / Charge / Absorb / Equalized / Fully charged / Fall back
Battery temperature
°C
Reads battery temperature from sensor placed in the battery bank.
Total throughput
kWh
Total energy that has passed through the battery bank(s), based on the discharge current. Since commissioning or last reset. Can be reset under battery configuration.
Battery charge current
A
Total current going in and out of the battery bank(s). A negative current indicates discharge and a positive current indicates charge.
Battery capacity
Ah
Total battery bank max capacity. Depending on battery configuration this either shows the specified maximum capacity or dynamically estimates the maximum capacity.
Charge mode
Normal charge / Full charge / Extended Full Charge / Safe Mode / Ramp Up / Synchronize
Shows what charge mode that is currently active.
Charge request
Not active / Active
When active, eSite requires power to charge the batteries.
Cooling Fan status
Off / On / Forced On / Fall back
Battery charge strategy
Voltage control / Static SOC/ Partial SOC/ Li-ion Static / UPS AC Mode
Voltage Cycle Start
V
Voltage level to trigger charge cycle.
Voltage Cycle Stop
V
Voltage level for charge done.
Voltage Cycle Stop Current
A
Charge current for charge done.
Voltage Cycle Stop Time
sec
Charge time after reaching stop voltage and stop current.
Voltage Cycle Full Charge Time / Time Left
sec
Time between full charge cycles and time left until a full charge is triggered.
Voltage Cycle Full Charge Energy / Energy Left
kWh
Energy throughput between full charge cycles and throughput left until a full charge is triggered.
Static SOC Window start
%
SOC level to start charge.
Static SOC Window stop
%
SOC level to stop charge.
Static SOC Window Full Charge Time / Time Left
sec
Time between full charge cycles and time left until a full charge is triggered.
Static SOC Window Full Charge Energy / Energy Left
kWh
Energy throughput between full charge cycles and throughput left until a full charge is triggered.
Partial SOC Window
%
Falling SOC window to start charging.
Partial SOC Stop Current
A
Current level for charge done.
Partial SOC Stop Voltage
V
Voltage level to stop charging.
Partial SOC Stop SOC
%
Falling SOC window between charge cycles.
Partial SOC Full Charge Voltage
V
Lower voltage level to force full charge.
Partial SOC Full Charge Time / Time Left
sec
Time between full charge cycles and time left until a full charge is triggered.
Partial SOC Full Charge Energy / Energy Left
kWh
Energy throughput between full charge cycles and throughput left until a full charge is triggered.
Hybrid Shifting Status
enum
Peak Load Shifting status
enum
BMU data / Status
enum
The status can be: "Invalid", "Not installed", "No communication", "Operational", "Not Operational".
BMU data / SOC
%
State of Charge for each BMU.
BMU data / SoH
%
State of Health for each BMU.
BMU data / Current
A
Total current going in and out of the battery BMU. A negative current indicates discharge and a positive current indicates charge.
BMU data / Max Cell Voltage
V
Maximum Cell Voltage.
BMU data / Min Cell Voltage
V
Minimum Cell Voltage.
BMU data / Total Voltage
V
Total Voltage of the Module.
BMU data / Charge mode
-
Charge mode of the module can be charge or discharge.
Two gensets can simultaneously be connected to eSite x10. The configured gensets are visible under the Genset menu. The Genset menu provides the information shown in the table below. For further information about Gensets read the reference in section Genset.
Operational mode
Forced on / All AC sources forced off / Auto
Actual genset operational mode commanded by the eSite x10.
Night Silence mode
Disabled / Inactive / Pre charge / Silent period active / Silent period aborted
If Night Silence mode is active, the genset is inhibited until it leaves night silence or Night Silence is aborted.
Genset mode
Ready / Start Request / Warm-up / Ramp Up / Running / Ramp Down / Cool Down / Off
eSite controlled state of the genset(s). A counter shows for how long a mode has been active, for example for Running, or how many seconds that are left, for example for Warmup.
Actual state
Stopped / Running
Detected state of the genset.
Unexpected genset start
Yes / No
Genset is running without eSite requesting it to run.
Power request
W
Requested power from the genset, kept at maximum capacity rating.
Genset power
W
Produced power from genset.
Produced energy
kWh
Produced energy since commissioning or last reset.
Produced current
A
Produced current from genset.
L1
V (Hz)
Voltage and frequency.
L2
V (Hz)
Voltage and frequency.
L3
V (Hz)
Voltage and frequency.
Genset service countdown
h
Time left until genset service.
Total genset run hours
h
Runtime since eSite x installation.
Tank X volume
l
Present volume in tank.
Tank X max volume
l
The maximum volume of the tank is configured under the configuration menu Fuel monitoring.
Three solar arrays at a time can be connected to eSite x10. All connected solar arrays are visible under the Solar menu. The Solar menu provides the information shown in the table below. For further information about solar arrays read the reference in section Solar management.
Total power
W
Total produced power from the solar converters.
Total energy
kWh
Total produced energy from the solar converters since installation/last energy reset.
Total current
A
Total produced output current from the solar converters.
Array voltage (Solar x)
V
Voltage of a specific array.
Output power (Solar x)
W
Produced power from the array.
The Grid menu provides the information shown in the table below. For further information about Grid read the reference in section Grid.
Grid status
Invalid / Inhibited / Partial / Ok
Invalid when no grid power is available, Inhibited if Green Power mode is configured to inhibit grid power, Partial 1 or 2 phases are not available.
User grid power
0–10500 W
Power drawn from grid.
Total used grid energy
kWh
Energy drawn from grid since installation of the site.
Grid current
A
Produced current from grid.
L1
V (Hz)
Voltage and frequency.
L2
V (Hz)
Voltage and frequency.
L3
V (Hz)
Voltage and frequency.
Grid fuse
A
Configured size of the maximum rating of the fuse on site.
The Web Alarm menu provides the alarms that are active on site. For a full alarm description with actions see section Alarm list. The Web Alarm menu provides information about Active alarms and the time when an alarm is activated.
The Web Graph provides the graphs shown in the table below. Enter the number of days to display in the graphs and click Submit. The default graphs present data for a period of one day.
Graph – Temperatures
Shows Connection Compartment, battery and outside temperature for the chosen amount of days.
Graph – Power
Shows consumed power, genset 1–2, grid and solar power for the chosen amount of days.
Graph – Grid
Shows grid voltage and current for the chosen amount of days.
Graph – Genset 1–2
Shows genset voltage and current for the chosen amount of days.
Graph – Battery
Shows system voltage, battery voltage, state of charge and charge current for the chosen amount of days.
Graph – Tank Volume
Shows tank volume for the chosen amount of days.
The graphs provides data for a certain period in order to perform troubleshooting and to interpret the alarms. The example in figure 4.3 shows the recorded temperature data for a period of ten days.
The About menu provides the information shown in the table below.
Software Versions
– Main controller SW Version - Linux Version
Main Controller Information
– System Cpu Load - System Cpu RAM Usage - System Cpu Temperature - System Sys Disk Usage - System Data Disk Usage - System Uptime - MAC address
HW Info
– Main compartment serial number - Modem signal strength
License Information
Information about open source software components that are used.
If the modem signal is acceptable, the modem signal strength is displayed in dB. If there is an error it is shown under this menu.
Under the Configuration tab, the settings required for eSite x10 and its associated systems are made.
Current settings and values are visible in the 'Current value' column. To update settings and values, enter the new information in the column Set and click Save to confirm the update. The Save button must be clicked for each configuration.
Use this configuration menu to change the name, location and time of eSite x10.
eSite name
Not Commissioned
-
Name of the site.
Longitude
0.0
Longitude range -180 to 180
Enter as decimal degrees. Use format (-)xx(x).xxx(xx).
Latitude
0.0
Latitude range 90 to 90
Enter as decimal degrees. Use format (-)xx(x).xxx(xx).
Select time zone
Africa /Libreville
N/A
Select correct time zone from the drop down list.
Time/Date
N/A
Year - Month - Day Hour : min : sec
The last known local time is automatically used.
Connection Compartment Serial Number
0
-
-
x10 Expansion
No Expansion installed
ACDC Expansion installed
Enable if x10 Expansion unit is installed
Use this configuration menu when connecting eSite x10 to a specific eSite Tools server.
eSite Tools ID
Not Commissioned
–
Must be unique for the site. Used to reference the site by eSite Tools server.
eSite Tools server IP
0.0.0.0
–
IP address to eSite Tools server. Provided by eSite Power Systems
eSite event time
20 sec
–
The time between events is synchronized between eSite x10 and eSite Tools.
IP number to NTP server
pool.ntp.org
–
Retrieves correct time using network Time Protocol (NTP).
Enable eSite Tools server time
Off
Off / On
Use server time locally on site. The server time can differ from local site if the server is placed in another time zone.
Restart eSite Tools agent
–
–
Restarts eSite Tools agent. After a restart it directly tries to establish a connection to the server.
Start eSite Tools communication test
-
-
This will start the communications test to eSite Tools. A log file is created and will be included in the backup archive, goto 'System' menu to backup data. The test can take up to 75 seconds.
Use this configuration menu when updating the I/O settings. For more information about I/O see 8.12.4 I/O screw terminals where the connection is made.
Source A
AC grid
No Source / AC grid / AC genset 1
Type of AC source connected to input A.
Source B
No source
No Source / AC grid / AC genset 2
Type of AC source connected to input B.
Number of external Battery Current Sensor
No External Sensor
No External Sensor / One Sensor installed / Two sensor installed
At least one current sensor for each battery string is need to be mounted if an expansion unit is installed.
Battery 1 CAN sensor
ID 3C1
ID 3C1-3C9
Important to connect correct ID to the battery CAN sensor.
Battery 2 CAN sensor
ID 3C1
ID 3C1-3C9
Important to connect correct ID to the battery CAN sensor.
Battery Bank 1 MCB
Normally closed
No input / Normally closed / Normally open
When tripped the system is set to safe mode and an alarm is triggered.
Battery Bank 1 MCB
Normally closed
No input / Normally closed / Normally open
When tripped the system is set to safe mode and an alarm is triggered.
Battery Bank Door Alarm
Normally closed
No input / Normally closed / Normally open
When tripped an alarm is triggered.
Surge Protection Alarm
No input
No input / Normally closed / Normally open
Used with external surge protection alarm. Check the I/O list for the connection. When tripped an alarm is triggered.
Aux Rectifier Alarm
Normally closed
No input / Normally closed / Normally open
Used with external rectifier alarm. Check the I/O list for the connection. When tripped an alarm is triggered.
Battery Voltage Sensor
Battery Voltage Sensor
Internal Voltage Sensor/Battery Voltage Sensor
Select which sensor to be used as battery voltage sensor. Internal uses x10 voltage sensor inside unit. Battery Voltage Sensor uses external battery voltage cables as sensor
Genset 1–2 Alarm 1–3
No input
No input / Normally closed / Normally open
When tripped an alarm is triggered. Used for alarms coming from the genset using alarm relays. Same configuration can be found under section 'Genset'
Digital Inputs 1–8
No input
No input / Normally closed / Normally open
Configures the digital input to its corresponding relay wiring. If set to "No Input" alarms are not triggered.
4.9.5.2 Outputs
Digital Output 1
Genset 1 start cmd
Not configurable
Used for genset start
Digital Output 2
Not used
Genset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay
*See comments below.
Digital Output 3
Green CC LED
Genset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay
*See comments below.
Digital Output 4
Red CC LED
Genset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay
*See comments below.
Digital Output 5
Not used
Genset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay
*See comments below.
Digital Output 6
Not used
Genset 1 start cmd / Genset 2 start cmd / Green CC LED / Red CC LED / Cabinet Cooling / Alarm relay
*See comments below.
Digital Output 2-6 State
Normally open
Normally closed / Normally open
Function of the digital out relay.
Alarm Relay 2-6
None
Choosing one alarm from the list will trigger an alarm on digital out relay.
*The digital out relays can be used to trigger an external alarm. The relay should not be connected directly to the alarm due to the current limitation through the relay. See 8.12.4 I/O screw terminals for more details.
Use this configuration menu to change the genset configuration. All gensets connected to eSite x10 are visible here, named Genset 1 and Genset 2. Click the genset to configure. This option is also used to update the Night Silence configuration.
Night silence enable
Off
Off / On
Enables Night Silence mode.
Start time
20:00
00:00 – 23:59
Start time for silent period. The batteries are pre-charged before this time.
Stop time
08:00
00:00 – 23:59
Stop time for silent period. The genset is allowed to start.
Stop voltage level
46.8 V
0 – 60 V
If the battery voltage falls below this value the genset is allowed to start and the silence period ends. Only applicable if stop on charge request is disabled.
Stop SOC level
0
0 – 100 %
If the SOC level falls below this value the genset is allowed to start and the silence period ends. Only applicable if stop on charge request is disabled.
Min Capacity Left
150 Ah
0 – 9999 Ah
Night silence mode will end when a charge request becomes active
Stop on charge request
On
Off / On
Select if a charge request is allowed to start the genset and end the night silence period.
Enable Exercise Run
Off
Off / On
Enable the genset exercise run
Interval between starts
360 hours
0 – 9999 h
Minimum interval between genset starts.
Genset run duration
1800 sec
0 – 9999 s
Genset running time.
Genset start alarm delay time
300 sec
1-9999 s
Genset Failed to Start/Stop Alarms are trigged when the conditions are fulfilled after this time. Setting this time to a low value in a dual genset system will result in a quicker genset start. Recommended in UPS mode.
Operational mode
Auto
Auto / Genset Forced on / All AC sources Off
Used to force genset on from eSite. It is recommended to always leave operational mode in Auto.
Genset rated power
15 kVA
0 – 30kVA
Rated power of genset. The power should not be set higher than the genset capacity. When calculate the genset rated output, only 70% of the total capacity is used.
Genset warm up
10 sec
0 – 600 sec
Time from genset start until power is drawn from it.
Genset ramp up
30 sec
0 – 600 sec
Time for gradually increasing power demand from genset.
Genset ramp down
30 sec
0 – 600 sec
Time for gradually decreasing power demand from genset.
Genset cooldown
60 sec
0 – 600 sec
Time the genset is running without any power demand before it is commanded off.
Genset service time
250 h
0 – 9999 h
Alarm is trigged when this number of hours is left until service.
Genset Alarm 1–3
No input
No input / Normally closed / Normally open
When tripped an alarm is triggered. Used for alarms coming from the genset using alarm relays. Same configuration can be found under section 'I/O'.
Genset service time reset
N/A
Reset function
Resets service time. The service time is presented on the genset page.
Genset run time reset
hours
Set/Reset function
Set the genset runtime to a value.
Genset service time alarm
0 h
0 – 1 000 h
Hours left until the service alert informs. Available only if the alarm is enabled.
Genset service time alarm enable
Disabled
Enabled / Disabled
Enable the service time alarm.
Activate Genset control panel communication
Disabled
Enabled / Disabled
Slave ID
1
1 – 255
The slave ID must match the slave ID setting on the genset panel.
Restart Modbus communication after changes
–
–
A restart after change of settings.
A set of signals can be configured to be read from the genset panel if they are supported from the genset panel. The following settings must be done for each signal according to the genset panel Modbus communication specification. See the Appendix For installation guide.
Function
No_Function / Read_Holding_Registers / Read_Input_Registers
Select the correct function according to genset panel.
Register
0 – 99 999
The signal register.
Type
BOOLEAN / UINT8 / UINT16 / INT16 / UINT32 High word first / INT32 High word first / UINT32 Low word first / INT32 Low word first IEEE–754
Select the signal type.
Scale
No scale, 10, 100, 1000, 3600
For signal scaling.
Bit position
1 – 16
Select the bit position.
Maximum grid phase current
19 A
0 – 19 A
Current limitation for the grid fuse of a single phase.
Green Power Influx Enabled
Off
On / Off
Enables Green Power mode.
Green Power Mode
Load percent
Load Percent / Time Interval / AC Power Minimization
Allows the user to choose between the three available operational modes.
Voltage Activation
49V
0 – 60 V
Battery voltage required for activation of green power influx function.
Voltage Deactivation
47 V
0 – 60 V
If the battery voltage goes below this value, Green Power mode is deactivated and the AC source must complete it's charge cycle before Green Power mode is reactivated.
SOC Level Activation
60 %
0 – 100 %
If Green Power mode is inactive due to low SOC , it is activated when the SOC reaches this value.
SOC Level Deactivation
50 %
0 – 100 %
Green Power mode is deactivated if the SOC level falls below this value.
Activation Delay Timer
60 s
0 – 3 600 s
Time needed to ensure that solar power is stable and sufficient.
Solar Load Deactivation
70 %
0 – 200 %
Solar power percentage of customer load required for solar to be considered sufficient. If Green Power mode is active, it is deactivated when the solar power drops below this limit. If Green Power mode is inactive, it is activated when this limit is exceeded and the specific mode requirements are met.
Solar Load Activation
80 %
0 – 200 %
Solar power percentage of customer load required for Green Power mode deactivate.
AC Source Disable Time
07:00
00:00 – 23:59
Green Power mode is activated, AC sources are disabled.
AC Source Enable Time
16:30
00:00 – 23:59
Green Power mode is deactivated, AC sources are re-enabled.
Minimum SOC
40 %
0 – 100 %
Minimum SOC threshold for allowing AC Power in AC Minimization mode.
Minimum SOC Hyst.
2 %
0 – 100 %
Minimum SOC hysteresis in SOC % for controlling AC Power inhibits in AC Minimization mode.
Enable external solar 1 and 2
Off
On / Off
Select "On" only if an external solar is installed on site.
Solar 1 and 2 CAN sensor
No External Sensor
No External Sensor / ID 3C1 - 3C9
Set Solar 1 and 2 current sensor CAN ID. Make sure the ID is not in conflict with other CAN sensors.
Cabinet Cooling can be configured in two different modes, see table below. The digital output relay need to be configured to 'Cabinet Cooling', see I/O Configuration
Cabinet Cooling mode
No Cabinet Cooling
No Cabinet Cooling, Delta Ambient, Battery temp levels
Delta Ambient mode uses temperatures offsets between battery and ambient temp. Battery Temp Level mode use an temperature set value.
Fan On Delta mode (°C)
8°C
0-100°C
Temperature difference threshold for turning on battery cooling.
Fan Off Delta mode (°C)
2°C
0-100°C
Temperature difference threshold for turning off battery cooling.
Fan On Level mode (°C)
32°C
0-100°C
Temperature threshold for turning on battery cooling.
Fan Off Level mode (°C)
25°C
0-100°C
Temperature threshold for turning off battery cooling.
Min Fan Runtime (sec)
300
10000 (sec)
Minimum runtime for battery cooling fan before it can be turned off.
Manually start cooling fan
Current output value
Auto, Cooling Fan On
The output value can be: Off, On, Forced On, Fallback (temp sensor in fallback)
Use this configuration menu to change the Fuel monitoring. All tanks connected to eSite x10 are visible here, named Tank 1 and Tank 2. Click the tank to configure. Two tanks can be installed with fuel monitoring with support for different types of sensors. A sensor with an output can be connected to an Analogue In on the I/O screw terminals. The measuring range of the Analogue In is 0 – 10 V. eSite x10 can also read fuel data from the genset panel if a fuel sensor is integrated with the genset. See section Genset Management.
Sensor type
No fuel sensor
No fuel sensor / Volt–height / Volt-litre / Lookup volt-litre
All counters for consumption, fillings and losses are reset when no fuel sensor is selected. Volt–height is used for standard sensor with an voltage output corresponding to pressure or height. Volt–litre is used with sensors that have an voltage output corresponding to litres. Lookup volt – litre is used for example on tanks of irregular shape.
Tank shape
Rectangular box
No tank / Rectangular box / Standing cylinder / Horizontal cylinder
Shape of the tank.
Tank height
0 mm
0 – 10 000 mm
Enter the values as accurately as possible. Do not round off numbers.
Tank length
0 mm
0 – 10 000 mm
Enter the values as accurately as possible. Do not round off numbers.
Tank width
0 mm
0 – 10 000 mm
Enter the values as accurately as possible. Do not round off numbers.
Tank radius
0 mm
0 – 10 000 mm
Only available for cylindrical tank types. The radius can be calculated by measuring the circumference and divide by 2π.
Sensor max height
1 884 mm
0 – 10 000 mm
For pressure sensor the height is calculated as: h = P/(ρg) where P is pressure in Pasqual (Pa). In the fuel sensor datasheet the range can be specified in Pa, Bar mH 2 O etc. Default for g is 9.812 and the density of diesel (rho) is 866 kg/m 3 . The density of diesel can vary.
Sensor output volt min
0.1 V
0 – 10 V
If a sensor with voltage as output is selected these settings must be set.
Sensor output volt max
10 V
0 – 10 V
If a sensor with voltage as output is selected these settings must be set.
Enable tenant 1 – 6 current sensor
Off
On / Off
If a tenant sensor is installed, set to "On".
Configure CAN ID
ID 0-9
ID 3C0 - 3C9
Each tenant sensor has to be configured with the correct sensor ID. Use the dropdown list to select the correct CAN ID.
Total load high power alarm
10 000 W
0 – 21 000 W
Combined power for both LP and HP and for all tenants. Must be active for 10 seconds. Threshold for high load alarm.
Tenant 1 – 6 high power alarm
5 000 W
0 – 9 500 W
Only active if tenant current sensor is "On". Must be active for 10 seconds. Threshold to trigger high power alarm.
Use this configuration menu to change the Battery settings. For custom battery configuration see below.
Battery configuration
NONE
–
A battery template must always be selected. Select it from the dropdown list and press the button. Imported battery configurations will be visible at the end of the list.
Import battery configuration
–
–
Export battery configuration
–
–
Battery charge strategy
Voltage cycle
Voltage cycle Static SOC Partial SOC UPS AC mode
Start a full charge cycle
–
–
Manually trigger a full charge cycle. Recommended for new batteries. When started, system mode reports Auto Full Charge and charge mode on battery page reports Full Charge.
Start an extended full charge cycle
–
–
Manually trigger an extended full charge cycle. When started, system mode reports Auto Full Charge and charge mode on battery page reports Extended Full Charge.
Start Balancing Full Charge cycle
–
–
Manually trigger a Balancing Full Charge cycle for Li-ion batteries. When started, system mode reports Auto Full Charge and charge mode on the battery page reports Balancing Full Charge.
Reset number of charge cycles
–
–
Reset number of completed charge cycles (Li-ion batteries only).
Enable Periodic Balancing Full Charge
–
–
Enable periodic Balancing Full Charge cycles (Li-ion batteries only).
Balancing Full Charge Energy Throughput
–
–
Energy throughput between Balancing Full Charge cycles (Li-ion batteries only).
Balancing Full Charge Number of Cycles Interval
–
–
Number of charge cycles between Balancing Full Charge cycles (Li-ion batteries only).
Alarm Battery High Temp
°C
See data sheet of battery
Above this level an alarm is triggered
Alarm Battery Very High Temp
°C
See data sheet of battery
Above this level an alarm is triggered
Alarm Battery Low Voltage
V
0-60V
Low voltage alarm
Alarm Battery Low Voltage Reset
V
0-60V
Low voltage alarm reset
Reset Battery Total Throughput
–
–
Reset Battery Total Throughput
Set new battery configuration name
-
any text > 3 letters
Set any name to the configuration setup, especially when the configuration shall be exported to other sites but not a requirement.
Rated Capacity
Ah
See data sheet of battery
Rated of the battery string/BMU
Coulomb Efficiency
See data sheet of battery
Coefficient for compensating Ah round trip efficiency during charging. % * 0.01
Absorb Voltage
V
Genset/Grid boost voltage – 0.5V
Absorb voltage threshold
Absorb Time
sec
300 s
Absorb time(s)
Absorb To Charge Voltage
V
Genset/Grid float voltage – 0.5V
Fall back voltage
Equalize Current
A
Rated Battery Capacity * 0.03
Equalize current
Equalize Time
sec
21600 (6h)
Equalize time(s)
Fully Charged Current
A
Rated Battery Capacity * 0.03
Full charge current
Fully Charged Time
sec
60
Fully charged time(s)
Temperature Compensation X0-X3
°C
X1>X0, X2>X1, X3>X2
Temperature compensation, X values, must be increasing with the lowest value in X0.
Temperature Compensation Y0-Y3
V
See data sheet of battery
Voltage compensation, Y values
Extended Full Charge Time
sec
64800 (18h)
Extended full charge time(s)
Genset Boost Voltage
V
See data sheet of battery. Max 58V
Boost voltage (topping charge with constant voltage level)
Genset Float Voltage
V
See data sheet of battery
Float voltage
Grid Boost Voltage
V
See data sheet of battery. Max 58V
Boost voltage (topping charge with constant voltage level)
Grid Float Voltage
V
See data sheet of battery
Float voltage
Solar Boost Voltage
V
Genset/Grid boost voltage + 0.2V
Solar boost voltage
Solar Float Voltage
V
Genset/Grid float voltage + 0.2V
Solar float voltage
Nominal Current
A
Rated Battery Capacity * 0.2
Nominal battery charge current. VRLA: Total battery block current.
Maximum charge current
A
Rated Battery Capacity * 0.2
Battery charge current. Lithium-Ion: Set current upon total block size. Use current limit information from Li-ion batteries if present on com bus.
Safe Mode Current
A
Same as Nominal Current
Used when the system is in an abnormal state
Safe Mode Voltage
V
< Float Genset Voltage
Used when the system is in an abnormal state
Start Voltage
V
See data sheet of battery
Voltage level for charge start.
Stop Voltage
V
See data sheet of battery OR Boost Voltage - 1V
Voltage level for charge done. Stop when Voltage and Current are fulfilled.
Stop Current
A
See data sheet of battery OR Rated Battery Capacity/100
Current level for charge done. Stop when Voltage and Current are fulfilled.
Stop Time
sec
See data sheet of battery
Charge time(s) after reaching stop voltage/current
Full Charge Time
sec
864000 (10 days)
Time(s) between full charge cycles
Full Charge Energy
kWh
Rated Battery Capacity * 1.18
Energy throughput between full charge cycles
Start SOC
percent
See data sheet of battery
SOC level to start charge
Stop SOC
percent
See data sheet of battery
SOC level to stop charge
Full Charge Voltage
V
See data sheet of battery
Lower voltage level to force full charge
Full Charge Time
sec
864000 (10 days)
Time(s) between full charge cycles
Full Charge Energy
kWh
Battery Capacity * 1.18
Energy throughput between full charge cycles
SOCWindow
percent
See data sheet of battery
Falling SOC window to start charging
Stop Current
A
See data sheet of battery OR Rated Battery Capacity/100
Current level for charge done. Stop when Voltage and Current are fulfilled.
Stop Voltage
V
See data sheet of battery OR Boost Voltage - 1V
Voltage level for charge done. Stop when Voltage and Current are fulfilled.
Inhibit Stop Charging
percent
35 %
Lower SOC level to keep charge request
Full Charge Voltage
V
See data sheet of battery
Lower voltage level to force full charge
Full Charge Time
sec
864000 (10 days)
Time(s) between full charge cycles
Full Charge Energy
kWh
Rated Battery Capacity * 1.18
Energy throughput between full charge cycles
Dual Genset Run Interval
sec
21600 s (6 h)
The time in seconds the genset shall run before switching genset. Max 99999999 s
Periodic Full Charge Enabled
–
Disabled
Enable the periodic full charge option
Full Charge Duration
hours
12 h
The time in hours the system shall run the genset in full charge mode.
Interval between Full Charge
hours
2160 h (90 days)
Time between full charge cycles.
Full Charge Trigger Voltage
V
45.5 V
Minimum=45 V, Maximum=60 V.
4.9.12.2 Lithium-ion battery parameters.
Set new battery configuration name
-
any text > 3 letters
Set any name to the configuration setup, especially when the configuration shall be exported to other sites but not a requirement.
Rated Capacity
Ah
See data sheet of battery
Rated of the battery string/BMU
Coloumb Efficiency
See data sheet of battery
Coefficient for compensating Ah round trip efficiency during charging. % * 0.01
Genset Set Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using genset power
Genset Float Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using genset power
Solar Set Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using solar power
Solar Float Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using solar power
Grid Set Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using grid power
Grid Float Voltage
V
See data sheet of battery.
Used in Lithium-Ion settings when using grid power
Enable Battery Synchronization
-
Disabled
Enable battery synchronization at the end of a charge cycle.
Battery Synchronization Current
A
0 A
Battery synchronization charge current limit.
Battery Synchronization Time
sec
300 s
Battery synchronization step duration.
Battery Ramp Up Voltage
Volt
50 V
Battery ramp up start voltage.
Battery Ramp Up Time
sec
1s
Defines the rate of voltage increase during ramp up. 1 Volt per configured time interval
Safe Mode Current
A
Same as Nominal Current
Used when the system is in an abnormal state
Safe Mode Voltage
V
< Float Genset Voltage
Used when the system is in an abnormal state
Enable Hybrid Shifting
-
Disabled/Enabled
Set Shifting On time
hh:mm
-
Time setting to activate hybrid shifting.
Set Shifting Off time
hh:mm
-
Time setting to deactivate hybrid shifting.
Genset stop voltage
V
-
Genset stop Voltage in Hybrid shifting mode.
Enable Peak Load Shifting
-
Disabled/Enabled
Set Shifting On time
hh:mm
-
Time setting to activate peak load shifting.
Set Shifting Off time
hh:mm
-
Time setting to deactivate peak load shifting.
Grid Float voltage
V
-
Grid Float Voltage in Peak Load shifting mode.
Charge State Current
A
1A
Battery charge current threshold to be exceeded for the battery to be in Charge state.
Discharge State Current
A
-1A
Battery discharge current threshold to fall below for the battery to be in Discharge state.
Charge Time
sec
10s
Duration of charge or discharge current conditions to be valid until battery state changes.
Fully charged cut off
A
Rated Battery Capacity * 0.04
Threshold of battery charge current to fall below for the battery to be considered fully charged..
Fully charged voltage
V
See data sheet of battery
Threshold of battery voltage to be exceeded for the battery to be considered fully charged.
Fully charged time delay
sec
60 s
Duration of the battery fully charged current AND fully charged voltage conditions to be met for the battery to be considered fully charged.
Equilibrium Voltage
V
0.1 V
Limit of voltage increase/decrease rate for the battery to be considered to be in Equilibrium state.
Equilibrium Time
sec
300 s
Duration of low voltage increase/decrease rate for the battery to enter Equilibrium state.
Start Voltage
V
See data sheet of battery
Voltage level for charge start
Stop Voltage
V
See data sheet of battery
Voltage level for charge done. Stop when Voltage and Current are fulfilled.
Stop Current
A
See data sheet of battery
Current level for charge done. Stop when Voltage and Current are fulfilled.
Stop Time
sec
See data sheet of battery
Charge time(s) after reaching stop voltage/current
Start SOC
percent
See data sheet of battery
SOC level to start charge
Stop SOC
percent
See data sheet of battery
SOC level to stop charge
Static SOCcontrol options
-
2
1 = Start/stop on average SOC, 2 = Protective SSOC with active comm. Start/stop on min/max BMU SOC, 3 = Balancing SSOC with active comm. Start/stop on min/min BMU SOC.
Balancing Full Charge Trigger Voltage
V
45.5 V
Safety SOC level to trigger Balancing Full Charge
Low Prio load disconnect volt
V
42-60 V
Voltage to disconnect LP, default=45 V
Low Prio load disconnect time
sec
–
Time before LP is disconnected after disconnect thresholds are reached, default=300 s
Low Prio load reconnect volt
V
42-60 V
Voltage required to reconnect LP, default=48 V
Low Prio load reconnect time
sec
–
Time before LP is reconnected after reconnect thresholds are reached, default=30 s
Low Prio load reconnect current
A
0-200 A
Produced current required to reconnect LP, default=20 A
Low Prio load fast reconnect volt
V
42-60 V
Voltage required for fast reconnect of LP , default=52 V.
High Prio load LVD enable
-
Disabled
If enabled, LVD will use separate settings for High Prio load LVD. Disabled, LVD will use the same settings for High Prio load as for Low Prio load.
High Prio load disconnect volt
V
42-60 V
Voltage to disconnect HP, default=43.5 V
High Prio load disconnect time sec
sec
–
Time before HP is disconnected after disconnect thresholds are reached, default=5 s
High Prio load reconnect voltage
V
42-60 V
Voltage required to reconnect HP, default=48 V.
High Prio load reconnect time sec
sec
–
Time before LP is reconnected after reconnect thresholds are reached, default=5 s
The Modbus communication enables third party systems to communicate with eSite. Use this configuration menu to change the Modbus settings. For more information regards the server registry see separate manual "eSite x10 Modbus server".
Enable communication to Li-ion BMS
OFF
ON / OFF
Set to ON if communication to Li-ion BMS is installed.
Installed Li-Ion modules
0
1-255
Number of installed BMUs, used to set communication alarms and for communication to BMU.
Enable communication to Genset1 AMF panel
OFF
ON / OFF
Set to ON if communication to Genset1 is installed. Configuration needed in Genset tab.
Enable communication to Genset2 AMF panel
OFF
ON / OFF
Set to ON if communication to Genset2 is installed. Configuration needed in Genset tab.
Slave ID
0
1-255
The slave ID must not be in conflict with any ID on the Modbus.
Restart Modbus handler
–
–
Restart Modbus handler when changes are made.
Set Modbus / RTU or Modbus / TCP
RTU
RTU / TCP
Set Modbus server protocol.
Server port number
1502
1 – 9 999
Set Modbus server port number.
Server slave ID
1
1 – 999
Set Modbus server slave ID.
Enable Modbus server
Off
On / Off
Enable / disable Modbus server.
Restart Modbus server
–
–
Restarts Modbus server when changes are made..
Use this configuration menu when eSite x10 must be shutdown or restarted.
Reboot system
Reboot main controller.
Shutdown system
Shutdown main controller. To boot up after a shutdown, power to the Main Compartment must first be turned off.
Factory reset
Reset all configurations to default settings. eSite x10 will reboot afterwards.
Modem restart
Restart the modem.
Reset Load switch
If one or both of the LP and HP load breakers are tripped due to over-current, pressing the reset button will reset the breakers and reconnect the load.
Use this configuration option to perform a system update, backup data and upload configuration data.
See section System Update for more information.
Update eSite x10 controllers
Update the main controller, rectifier and solar controllers. Update images are provided by eSite Power Systems.
Backup data
Backup configuration data, custom battery file, Modbus configuration file and log data.
Upload configuration data
Upload a new battery file or configuration files received from eSite Power Systems here.
Update eSite x10 license
Change password
Select a user to change its password. Write the new user password in the text box and press 'Save'
Reset passwords
Reset passwords. Select a user and press 'Reset' button.
Add IP address/subnet mask
Add an extra ip address to eth0. Use syntax: xxx.xxx.xxx.xxx/nn where x is the IP address and nn is the subnet mask in Linux notation (24 = mask 255.255.255.0).
Add IP gateway
Add a gateway to eth0. Use syntax: xxx.xxx.xxx.xxx where x is the IP address to the gateway
IP Restore
Press to restore default IP settings
Change APN setting
Change the modem access point name (apn) from default (internet). Be patient, it takes 30 seconds to restart the modem with new settings.
This page forwards you to the site commissioning guide. During site commissioning eSite x10 configurations are finalized. The site commissioning makes sure that the eSite x10 is set up correctly and operates as intended.
Copyright © 2021 eSite Power Systems AB
X3 below the Bypass breakers
Serial number equal to and above 066
For more information see
The Fan can be forced on via command see Fall back status means that Ambient- and/or Battery-sensor are disconnected.
Shows what charge strategy is currently active. The battery charge strategy can be configured, for more information see section .
0=Not active, 1=Active. For more information see section .
0=Not active, 1=Active. For more information see section .
See section 6
Activates genset control panel communication. See the for more information.
Press the link to import a new battery configuration file. The file must have the extension '.flx' and been created via the Export link or supplied from eSite Power Systems. The new configuration will be visible at the end in the dropdown list. For more information on how to save a custom battery configuration file see section .
Press link to create new battery configuration file from current battery values. For more information on how to save a custom battery configuration file see section .
Different strategy will be visible depends on selected battery configuration. Reed section 8.4 for more information.
Hybrid shifting set a temporary genset stop value. See details in
Peak Load shifting set a temporary grid float value. See details in
Update the The file, which is provided by eSite Power Systems, must match the serial number of the eSite x10.