eSite x10 can be provided with AC power supply from genset and grid and with DC power supply from solar arrays. The supplied power is used to support customer load and to charge a battery bank. The AC power supply is converted into -48 V DC through rectifiers in the Main Compartment. The DC power supply is converted into -48 V DC through solar converters in the Main Compartment. Switching between the connected power sources is automatic through the patented silicone controlled rectifier (SCR) functionality. eSite x10 sends start and stop commands to the genset(s) automatically when required. If solar arrays are installed, they are under regulation from the internal solar converters at all times and will supply power when the weather conditions are favourable.
The Main Compartment contains:
Rectifier x 3
Solar converter x 3
SCR (replaces standard ATS)
Current, voltage, frequency and temperature sensors
Wi-Fi
GSM
Main Controller
Caution
The Main Compartment must be connected to the Connection Compartment only, unless a written statement from eSite Power Systems permits other connectivity devices. No third party connection device can be used without explicit consent and approval by eSite Power Systems. The Connection Compartment and the power connectivity is subject to regulatory control by eSite Power Systems.
Figure 3.1 shows an overview of a mounted eSite x10 unit with the most important features identified as follows.
A Mounting Frame B Main Compartment including Lower Main C Product marking plate G Connection Compartment lid D Visual indication – green LED E Visual indication – red LED F Connection Compartment G Connection Compartment lid
Figure 3.2 shows an overview of a complete site setup with the eSite x10 and associated systems on site, identified as follows.
A eSite x10 B eSite Tools C Battery cabinet and battery bank D Solar panels E Grid F Genset G Customer load
The list below outlines the options that are referenced in this manual. For a complete description of options, compatibility between options and what is included in each option package, see eSite x10 Standard and options document.
Enables connection of a second AC source. Switch between sources with solid state electronics. Current, voltage and frequency is measured from both sources.
Include 6kW solar converters. Advanced Solar MPPT control, Green Power Influx
Genset management, Genset Night Silence function, Genset Exercise run, Battery Charge strategies (Voltage Cycle, Static-SOC, Partial-SOC), Battery Monitoring (SOC, Battery capacity), UPS AC mode, Configurable Modbus client (AMF panels)
Pressure-based fuel level sensor for monitoring fuel consumption and anti-theft control.
Individual DC output monitoring: 6 x Tenant current measurement sensor. Tenant identification and energy consumption analysis.
Modbus server, SNMP
FOTA (Firmware Over-the-Air) upgrades, Remote configuration (eSite Tools), Remote monitoring, Alarm/Error event to NOC, Report services, Diagnostic
Support for battery cabinet cooling equipment with Delta Ambient and Battery Temp Level control options
Full integration of two (2) eSite x10 units for double rectifier capacity
Support for two (2) additional solar controllers (any brand)
Some options/features may be received as additional s/w patches. This may apply for already existing features or new features developed and customized upon request, based on customer requirements in coordination with the eSite development team.
These options are normally disabled from the standard software implementation and are not visible in any UI.
Contact eSite Power Systems to get more information regarding custom specific options.
Full Li-ion integration (any brand), Battery Charge strategies (Lion)
Full integration (any brand)