Wi-Fi not detected.
The Wi-Fi name is the same as the RMC serial number. Only Wi-Fi modules supplied by eSite Power Systems are allowed.
1. Verify that Wi-Fi is enabled on the smart phone/laptop.
2. Use another smart phone/laptop. If Wi-Fi connection continues to fail, use LAN cable to connect.
No connection established with LAN cable.
Connection to eSite Web is possible either through Wi-Fi or via LAN cable.
1. Verify that the IP of your laptop is set a static IP address 192.168.20.20.
2. Verify that the laptop network card is enabled.
3. Check that the LEDs next to the Ethernet port flashes. If not, try with another cable or laptop.
10.2.2 Solar
Solar array voltage but no output current is reported on eSite Web.
If any solar related alarms are active, the solar converter powers down, resets itself and tries to clear the alarm before starting to convert again. After reconnecting the solar array it can take up to 10 min before the array is detected and starts to produce power.
1. Check for any alarm on eSite Web and look up them up in the alarm list.
2. Verify that the solar panels and arrays are electrically floating and not connected to ground. The solar stand must be grounded separately.
3. Verify that the polarity is correct and not mixed up with neighbouring solar converters.
No Solar array voltage and no output current is reported on eSite Web.
1. Verify that the polarity is correct.
2. Check if there is array voltage on the input to the converters. Use a multimeter.
Output power from converter is lower than expected.
Cloudy weather, shade or dirty panels may cause poor performance.
1. Clean panels if necessary and/or remove objects that shade the panels.
2. Check solar array for damages. Even small damages might have a large impact on performance.
10.2.3 Other
Fuel sensor error.
Usually, large fluctuations indicate a broken sensor, bad connection or bad grounding. Some inaccuracy is expected due to uncertainties with tank dimensions, fuel density, fuel sensor etc.
1. Verify that the Fuel Sensor installation is done as instructed in the Fuel Sensor Installation manual.
2. Clean the air hose.
3. Clean the sensor.
4. Check for damages on the cable. Repair or replace if the cable is bent, squeezed or damaged in any other way.
5. Verify that the ground resistance is low.
No synchronization with eSite Tools.
GSM or 3G coverage is required on site. The eSite Modular system continues to operate without synchronization and buffers data until connection is established. Only GSM modules supplied by eSite Power Systems are allowed.
1. Check signal strength and possible error codes under the About menu on eSite Web.
2. Restart the modem under the Shutdown / Restart menu in eSite Web.
3. Verify configurations under the Setting/eSite Tools tab on eSite Web.
4. Verify that there is sufficient credit on the SIM card.
5. Test inserting the SIM card in a smartphone to verify that the PIN code is disabled.